Siemens SITRANS LR250 Instruction Manual page 84

Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

2.3.1.5. Minimum mA limit
Prevents the mA output from dropping below this minimum level for a
measurement value. This does not restrict the Failsafe or manual settings..
Values
2.3.1.6. Maximum mA limit
Prevents the mA output from rising above this maximum level for a
measurement value. This does not restrict the Failsafe or manual settings.
Values
2.3.1.7. 4 mA Output Trim
Calibrates the 4 mA output. The mA output of the device is pre-calibrated;
however, 4 mA Output Trim can be used to trim remote displays or inputs.
Values
Related
parameters
Steps:
1. Set mA Output Function Manual.
2. Set mA Output Value to 4 mA.
3. Attach a calibrated meter and check the output at the terminals; record
the remote reading in mA.
4. Enter this value in 4 mA Output Trim.
5. Restore mA Output Function to previous setting.
6. Confirm that the mA output is as expected.
2.3.1.8. 20 mA Output Trim
Calibrates the 20 mA output. The mA output of the device is pre-calibrated;
however, 20 mA Output Trim can be used to trim remote displays or inputs.
Values
Related
parameters
Steps:
1. Set mA Output Function to Manual.
2. Set mA Output Value to 4 mA.
3. Attach a calibrated meter and check the output at the terminals; record
the remote reading in mA.
4. Enter this value in 20 mA Output Trim.
5. Restore mA Output Function to previous setting.
6. Confirm that the mA output is as expected.
Page 80
SITRANS LR250 (HART) – INSTRUCTION MANUAL
Range: 3.8 to 20.5 (mA)
Default: 3.8 (mA)
Range: 3.8 to 20.5 (mA)
Default: 20.5 (mA)
Range: 2.0 to 6.0 (mA)
20 mA Output Trim
Range: 18.0 to 24.0 (mA)
4 mA Output Trim
7ML19985JE01