Installing The Cp, Connecting Power And Ground - Siemens CP 343-1 Lean Manual

Table of Contents

Advertisement

Suitable cables for temperatures in excess of 70 °C
If the cable or conduit entry point exceeds 70°C or the branching point of conductors
exceeds 80°C, special precautions must be taken. If the device is operated at ambient
temperatures above 50°C, the permitted temperature range of the selected cable must be
suitable for the temperatures actually measured.
Protection against transient voltage surges
Provisions shall be made to prevent the rated voltage from being exceeded by transient
voltage surges of more than 40%. This criterion is fulfilled, if supplies are derived from
SELV (Safety Extra-Low Voltage) only.
5.2

Installing the CP, connecting power and ground

Note
Pulling/plugging
Pulling/plugging the CP when the power is on is not permitted.
You should also remember that by removing a module from the rack, all modules on the
other side of it will be disconnected from the CPU.
CP 343-1 Lean
Manual, 10/2012, C79000−G8976−C198−07
WARNING
WARNING
Installation, connecting up and commissioning
5.2 Installing the CP, connecting power and ground
31