4-2.2.3
Determine What Components are Required
•
Cylinder size, quantity and fill requirements. Refer to Table 4-4 and Table 4-5.
•
Cylinder framing, mounting brackets, etc.
•
Detection and control equipment required.
•
Other system requirements, such as reserve supply, pressure switches, etc.
4-2.2.4
Locate Nozzles
Locate nozzles based on the following:
•
Ceiling height (16 ft [4.87 m] maximum, 1 ft [0.30 m] minimum).
•
Nozzle area coverage.
•
Special hazard area layout considerations.
4-2.2.5
Locate Cylinders
Locate cylinders based on the following:
•
Number of cylinders required.
•
Storage temperature/environmental considerations, such as weather, area classification
and corrosive environment.
•
Accessibility.
•
Floor loading.
4-2.2.6
Locate Piping
Locate piping based on the following:
•
Nozzle location.
•
Structural members for bracing the pipe.
4-2.2.7
Pipe Size and Layout
Determine pipe size and layout for the following factors:
•
Draw piping isometric.
•
Dimensions of all pipe sections.
•
Locate all fittings.
•
Note all elevation changes.
The preceding information will be entered into the computer program.
06-236115-001
4-7
Design and Installation
October 2014