4-2.2.3

Determine What Components are Required

Cylinder size, quantity and fill requirements. Refer to Table 4-4 and Table 4-5.
Cylinder framing, mounting brackets, etc.
Detection and control equipment required.
Other system requirements, such as reserve supply, pressure switches, etc.
4-2.2.4

Locate Nozzles

Locate nozzles based on the following:
Ceiling height (16 ft [4.87 m] maximum, 1 ft [0.30 m] minimum).
Nozzle area coverage.
Special hazard area layout considerations.
4-2.2.5

Locate Cylinders

Locate cylinders based on the following:
Number of cylinders required.
Storage temperature/environmental considerations, such as weather, area classification
and corrosive environment.
Accessibility.
Floor loading.
4-2.2.6

Locate Piping

Locate piping based on the following:
Nozzle location.
Structural members for bracing the pipe.
4-2.2.7

Pipe Size and Layout

Determine pipe size and layout for the following factors:
Draw piping isometric.
Dimensions of all pipe sections.
Locate all fittings.
Note all elevation changes.
The preceding information will be entered into the computer program.