1
GENERAL
To comply with NFPA 2001 (2012 ed.), all control head must be under placement supervision
such that, if an electric actuator is removed, an audible and visual signal will be initiated at the
control panel indicating system impairment. To accomplish this, Kidde is offering a Control
Head Monitor suitable for mounting between the electric control head and the corresponding
discharge valves.
This document provides instructions to install the Control Head Monitor.
For other details, see the Kidde Fire Systems
Agent: DIOM Rev BA, P/N 06-236115-001.
06-236115-003
®
ECS Fire Suppression System with HFC-227ea
1
July 2016