For US and Canada Explosion proof installations, seal all conduits within 18
inches from the end of the component.
WARNING
2.1.1
Standards for US Explosion Proof Approval
US Hazardous Location Markings:
•
Class I, Div 1, Groups CD
•
Class I, Zone 1, AEx d IIB T6
•
Class II, III, Div 1, Groups EFG
•
Zone 21, AEx tb IIIC T85°C
•
Ta = -40°C to 60°C
2.1.2
Standards for Canadian Explosion Proof Approval
Canada Hazardous Location Markings:
•
Class I, Div 1, Groups CD
•
Class I, Zone 1, Ex d IIB T6
•
Class II, III, Div 1, Groups EFG
•
Zone 21, Ex tb IIIC T85°C
•
Ta = -40°C to 60°C
2.2
Spacer, P/N 85-100000-002 (Optional)
A
spacer, P/N 85-100000-002, must be used when installing the Control Head Monitor between and
electric control head and the
See Section 2.2 for more information.
06-236115-003
Number
Issue Date
FM 3600
FM 3615
FM 3616
FM 3810
ANSI/ISA 60079-0
ANSI/ISA 60079-1
ANSI/ISA 60079-31
Number
CSA C22.2 NO. 0.4
CSA C22.2 NO. 0.5
CSA C22.2 NO. 25
CSA C22.2 NO. 30
61010-1
CAN/CSA 60079-0
CAN/CSA 60079-1
Stackable Pressure Operated Control head (P/N 82-878750-000)
3
2011
2006
2011
2005
2013
2013
2013
Issue Date
2013
2012
2014
2012
2012
2011
2011
.
July 2016
Need help?
Do you have a question about the ECS and is the answer not in the manual?