Kidde Fire Systems ECS Manual

Kidde Fire Systems ECS Manual

Fire suppression system
Table of Contents

Advertisement

Quick Links

This file contains the following:
Title
Manuals
Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: Design,
Installation, Operation and Maintenance Manual
Addenda
Supplement to Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent:
Design, Installation, Operation, and Maintenance Manual Rev BA, P/N 06-236115-001
Placement Supervision
Kidde Fire Systems 2" Valve and Safety Burst Disc Rebuild Kit and Instructions
Addendum
Supplement to Kidde Fire Systems® ECS Fire Suppression System with HFC-227ea
Agent: Design, Installation, Operation, and Maintenance Manual Rev BA, P/N 06-
236115-001 Stainless Steel Nozzles
November 2017
Part Number
Rev
06-236115-001
BA
06-236115-003
AB
06-237553-001
AA
06-236115-004
AA

Advertisement

Table of Contents
loading

Summary of Contents for Kidde Fire Systems ECS

  • Page 1 Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: Design, 06-236115-001 Installation, Operation and Maintenance Manual Addenda Supplement to Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: 06-236115-003 Design, Installation, Operation, and Maintenance Manual Rev BA, P/N 06-236115-001 Placement Supervision Kidde Fire Systems 2”...
  • Page 2 P/N 06-236115-001 October 2014 ® Kidde Fire Systems Fire Suppression System with HFC-227ea Agent: Design, Installation, Operation and Maintenance Manual LISTED APPROVED UL Listing File FM Approvals No. EX 4674 Project ID 3014861...
  • Page 4 Kidde-Fenwal disclaims any liability for any use that may be made of the data and information contained herein by any and all other parties. Kidde ECS Fire Suppression Systems with HFC-227ea Agent (Kidde ECS Systems) are to be designed, installed, inspected, maintained, tested and recharged by qualified, trained personnel in accordance with the following: •...
  • Page 5: Material Safety Data Sheets

    The Material Safety Data Sheets (MSDS) can be found in the Appendix A. The latest version of the MSDS can also be found online at the Kidde Fire Systems website (www.kiddefiresystems.com). Use the built-in navigation links to view the desired sheet.
  • Page 6: Safety Bulletin 1; March 2, 1987 Subject: Safe Cylinder Handling Procedures

    SAFETY BULLETIN 1; MARCH 2, 1987 SUBJECT: SAFE CYLINDER HANDLING PROCEDURES Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of violent discharge. This may result in serious bodily injury, death and property WARNING damage. BEFORE handling Kidde system products, all personnel must be thoroughly trained in the safe handling of the containers as well as in the proper procedures for installation, removal, filling, and connection of other critical devices, such as flex hoses, control heads, discharge heads, and anti-recoil devices.
  • Page 7: Safety Bulletin 2; May 1, 1993

    SAFETY BULLETIN 2; MAY 1, 1993 SUBJECT: SAFE CYLINDER HANDLING PROCEDURES FOR PRESSURIZED CYLINDERS Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of violent discharge. This will result in serious bodily injury, death and property WARNING damage.
  • Page 8 REMOVAL FROM SERVICE Remove all control heads, pressure operated heads, and pilot loops from cylinder valve, and attach protection cap to actuation port. Disconnect cylinders from system piping at the valve outlet. Disconnect valve outlet adapter, if used. Immediately install safety cap on valve outlet. Do not disconnect the cylinder from system piping if the safety cap is missing.
  • Page 9 THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 06-236115-001...
  • Page 10: Table Of Contents

    TABLE OF CONTENTS Foreword ....................... i Material Safety Data Sheets ................ii Safety Summary..................... ii Safety Bulletin 1; March 2, 1987 Subject: Safe Cylinder Handling Procedures ............iii Safety Bulletin 2; May 1, 1993 Subject: Safe Cylinder Handling Procedures For Pressurized Cylinders....iv Table of Contents....................
  • Page 11: Table Of Contents

    TABLE OF CONTENTS (CONT.) 3-3.4.1 Electric Control Heads, P/N WK-890181-000, P/N 81-890149-000, and P/N WK-890165-000 ............... 3-14 3-3.4.2 Electric/Cable Operated Control Heads, P/N 81-895630-000 and P/N WK-897494-000 .......... 3-16 3-3.4.3 Cable Operated Control Head, P/N 81-979469-000 ........3-17 3-3.4.4 Lever Operated Control Head, P/N WK-870652-000 ........3-18 3-3.4.5 Lever/Pressure Operated Control Head, P/N 82-878751-000 .......
  • Page 12 TABLE OF CONTENTS (CONT.) 4-2.2.2 Calculate the Volume of Protected Area............ 4-2 4-2.2.2.1 Adjusting for Altitude or Pressure ............4-3 4-2.2.3 Determine What Components are Required ..........4-7 4-2.2.4 Locate Nozzles..................4-7 4-2.2.5 Locate Cylinders ................... 4-7 4-2.2.6 Locate Piping..................4-7 4-2.2.7 Pipe Size and Layout ................
  • Page 13 TABLE OF CONTENTS (CONT.) 4-3.10.2 Multiple Cylinder System................ 4-27 4-3.10.3 Main and Reserve System ..............4-29 4-3.11 Installation of Electric Control Heads ............4-29 4-3.12 Installation of Pressure Operated Control Head, P/N 82-878751-000.... 4-31 4-3.13 Installation of Electric/Cable Operated Control Head, P/N 81-895630-000 and P/N WK-897494-000 ..........
  • Page 14 TABLE OF CONTENTS (CONT.) 5-4.3.3.2 Cylinders Equipped with Flexible Tape Liquid Level Indicator ....... 5-6 5-4.4 Inspection Procedures–2 Year ..............5-11 Inspection and Retest Procedures for HFC-227ea Cylinders ......5-11 5-5.1 Cylinders Continuously in Service Without Discharge ......... 5-11 5-5.2 Discharged Cylinders or Charged Cylinders That are Transported....
  • Page 15 TABLE OF CONTENTS (CONT.) CHAPTER 7 PARTS LIST Introduction and Parts List ..............7-1 Obsolete Parts ..................7-6 Discharge Nozzles ................. 7-7 7-3.1 UL Listed 360 Degree Nozzles..............7-7 7-3.2 UL Listed 180 Degree Nozzles:............... 7-9 APPENDIX A MATERIAL SAFETY DATASHEETS October 2014 06-236115-001...
  • Page 16: List Of Figures

    LIST OF FIGURES Figure Name Page Number HFC-227ea Pressure/Temperature Curve Isometric Diagram ........1-5 Typical HFC-227ea System with Electric Control Head ..........3-3 Typical HFC-227ea System with Cable Operated Control Head ........3-3 Typical Cylinder Assembly, 10 to 70 lb..............3-4 Typical Cylinder Assembly, 125 lb and 200 lb and 300 lb Manufactured through April 2014.
  • Page 17 Name Page Number Pressure Actuation Using Pressure from 1 Cylinder to Actuate a Maximum of Fifteen Sets of ECS Cylinders, Close Coupled......4-18 Installation of the Flexible Hose Directly into System Piping........4-22 4-10 Installation of Master Cylinder Adapter Kit............... 4-24 4-11 Single Cylinder Installation, Vertical Mounting (See Table 4-11) .........
  • Page 18 LIST OF TABLES HFC-227ea Select Physical Properties, U.S. Units ............. 1-5 HFC-227ea Select Physical Properties, Metric Units ........... 1-5 Container Temperature-Pressure Correlation (Based on a cylinder fill density of 70 lb./ft.3 or 1121 kg/m3) ........3-6 Cylinder, Equivalent Lengths ................. 3-6 Dimensions, HFC-227ea Cylinder/Valve Assemblies for Vertical Installation Only ..
  • Page 19 THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 06-236115-001...
  • Page 20: Chapter 1 General Information

    There are a number of limitations to these input parameters which must be observed if accurate results are to be obtained. Kidde ECS Fire Suppression Systems (Kidde ECS System) with HFC-227ea combine an environmentally safe fire suppression agent, highly effective detection devices and specially developed components for fast agent discharge.
  • Page 21: System Description

    1-2.1 General Kidde ECS Systems are used to suppress fires in specific hazards or equipment located where an electrically non-conductive agent is required, where agent cleanup creates a problem, where extinguishing capability with low weight is a factor and where the hazard is normally occupied by personnel.
  • Page 22: 1-2.1.2.2 Unbalanced System Agent Storage Container Temperature Range

    General Information 1-2.1.2.2 Unbalanced System Agent Storage Container Temperature Range In unbalanced systems, where agent flows through the nozzles at varying rates, the agent cylinder storage temperature range is 60°F and 80°F (16°C and 27°C). The latest version of the flow calculation software is written and tested for a 70°F (21°C) agent cylinder storage temperature (for more information see latest version of the Flow Calculation Software User’s Guide 06-236272-001).
  • Page 23: 1-2.2.2 Decomposition

    General Information 1-2.2.2 Decomposition When HFC-227ea is exposed to temperatures over approximately 1300°F (700°C), products of decomposition (halogen acids) are formed. If the HFC-227ea is discharged in 10 seconds or less, flames are rapidly extinguished and the amount of by-products produced is minimal. 1-2.2.3 Cleanliness HFC-227ea is clean and leaves no residue, thereby eliminating costly after-fire clean-up and...
  • Page 24: 1-2.2.5 Storage

    General Information 1-2.2.5 Storage HFC-227ea is stored in steel containers at 360 PSIG at 70°F (25 bar at 21°C) as a liquid with nitrogen added to improve the discharge characteristics. The pressure of the stored HFC-227ea varies substantially with temperature changes, as illustrated in Figure 1-1. When discharged, the HFC-227ea liquid vaporizes at the discharge nozzles and is uniformly distributed as it enters the fire area.
  • Page 25 THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 06-236115-001...
  • Page 26: Chapter 2 Operation

    Operation CHAPTER 2 OPERATION INTRODUCTION This chapter describes the controls and indicators for the Kidde ECS System. SYSTEM CONTROLS AND INDICATORS 2-2.1 General Compressed HFC-227ea liquid is held in the cylinder by a discharge valve. When the discharge valve is actuated by a control head, the valve piston is displaced and the compressed liquid escapes through the discharge port of the valve and is directed through the distribution piping to the nozzles.
  • Page 27: 2-2.3 Post-Fire Operation

    Operation 2-2.3 Post-Fire Operation After an HFC-227ea discharge, qualified fire suppression system maintenance personnel must perform post-fire maintenance as directed in Chapter 6 of this manual. Observe all warnings, especially those pertaining to the length of elapsed time before entering the hazard area. Do not enter a hazard area with an open flame or lighted smoking materials.
  • Page 28: Chapter 3 Component Description

    3-1.1 3 in Cylinder Valve In 2001, Kidde Fire Systems added a 3 inch discharge valve to its product line. This valve replaces the 2½ inch valves previously used on the 600 lb cylinder and is a standard fitting for the 900 lb cylinder assemblies (also new for the year 2001).
  • Page 29: Functional Description

    When the discharge valve is actuated, the compressed liquid agent discharges through the valve outlet and is directed through the distribution piping to the nozzles. The nozzles provide the proper flow rate and distribution of HFC-227ea. The Kidde ECS System is composed of the following components and assemblies: • Cylinder/valve assembly •...
  • Page 30 Component Description Fire Suppression Panel Electric Control Head PRESSURE OPERA TED SWIT CH 3P .D .T . Pressure Operated Valve Switch Pressure Gauge Liquid Level HFC-227ea Indicator Cylinder Nozzle Figure 3-1. Typical HFC-227ea System with Electric Control Head Pull Station FOR FIRE BREAK GLASS PULL HANDLE...
  • Page 31: Component Descriptions

    Component Description COMPONENT DESCRIPTIONS 3-3.1 HFC-227ea Cylinder/Valve Assemblies HFC-227ea is stored in steel cylinders as a liquid, superpressurized with nitrogen to 360 PSIG at 70°F (25 bar gauge at 21°C). The cylinder valve assembly is equipped with a supervisory pressure switch connection for monitoring cylinder pressure, a pressure gauge and a safety burst disc in compliance with DOT requirements.
  • Page 32 DISC ASSEMBLY Figure 3-6. 600 and 900 lb. Cylinder with 3" Valve The Kidde ECS System equipment listed herein is designed for an operating temperature range of 32°F to 130°F (0°C to 54°C). Table 3-1 shows the container temperature-pressure relationship based on a maximum fill density of 70 lb./ft.
  • Page 33: Container Temperature-Pressure Correlation

    Component Description Table 3-1. Container Temperature-Pressure Correlation (Based on a cylinder fill density of 70 lb./ft. or 1121 kg/m Nominal Charge, Temperature Pressure °F °C PSIG 19.9 20.9 22.2 15.6 23.5 21.1 24.8 26.7 26.3 32.2 27.7 37.8 29.3 43.3 48.9 32.7 54.4...
  • Page 34 Component Description As a reference guide, Table 3-2 provides the equivalent lengths for all the Kidde ECS System cylinder and valve assemblies. The numbers shown in the table represent the equivalent length through the cylinder valve with the flex hose or without the flex hose, depending on the application.
  • Page 35: Dimensions, Hfc-227Ea Cylinder/Valve Assemblies For Vertical Installation Only

    Component Description Table 3-3. Dimensions, HFC-227ea Cylinder/Valve Assemblies for Vertical Installation Only Valve Height Diameter Outlet Volume Height Part Number Valve w/LLI 90-10001X-001 1½" 17.3 0.44 7.07 0.18 0.167 0.0047 13.3 0.33 90-10002X-001 1½" 24.97 0.64 7.07 0.18 0.286 0.0081 0.53 90-10004X-001 1½"...
  • Page 36: Fill Range Hfc-227Ea Cylinder/Valve Assemblies For Vertical Installation Only

    Component Description Table 3-4. Fill Range HFC-227ea Cylinder/Valve Assemblies for Vertical Installation Only Gross Weight Empty Fill Range Weight Part Number Min. Fill Max. Fill 90-10001X-001 6-10 3-4.5 90-10002X-001 9-20 90-10004X-001 18-40 8-18 90-10007X-001 30-70 14-31.5 90-100121-001 54-125 24.5-56.5 90-100125-001 54-125 24.5-56.5 90-100200-101...
  • Page 37: Liquid Level Indicator

    Component Description 3-3.2 Liquid Level Indicator The optional Liquid Level Indicator (LLI) consists of a hollow metal tube inserted into a special fitting in the top of the 125, 200, 350, 600 or 900 lb HFC-227ea cylinder. See Table 3-5 for part number information.
  • Page 38: 3-3.3 Cylinder Mounting Equipment

    Component Description 3-3.3 Cylinder Mounting Equipment Steel straps and brackets are used to mount the cylinders in a vertical position. Cylinder straps (P/N WK-283945-000, WK-283934-000, 06-235317-001, WK-292971-000, WK-281866-000, WK-294651-000, and 06-236125-001) are available for all size cylinders (see Figure 3-11 and Table 3-6 and Table 3-7). F (hole size) Figure 3-11.
  • Page 39: Dimensions-Cylinder Mounting Straps, Metric

    Component Description Table 3-7. Dimensions–Cylinder Mounting Straps, Metric Cylinder Size Dimensions* Cylinder Part Number O.D. WK-283945-000 WK-283934-000 06-235317-001 125, 200 new style WK-292971-000 200 old style WK-281866-000 WK-294651-000 06-236125-001 *Note: Dimensions are in inches. Wall brackets (P/N 82-486485-000, 82-486486-000, 82-486487-000, and 82-486488-000) are available for the 10, 20, 40 and 70 lb size cylinders (see Figure 3-12 and Table 3-8 and Table 3-9).
  • Page 40: Dimensions-Cylinder Wall Brackets

    Component Description Table 3-8. Dimensions–Cylinder Wall Brackets Cylinder Dimensions* Capacity Part Number 82-486485-000 8.62 1.56 7.68 5.75 82-486486-000 14.37 7.31 7.68 5.75 82-486487-000 13.12 5.94 9.75 6.75 82-486488-000 19.62 12.44 9.75 6.75 *Note: Dimensions are in inches. Table 3-9. Dimensions–Cylinder Wall Brackets, Metric Cylinder Dimensions* Capacity...
  • Page 41: 3-3.4 Control Heads

    Component Description 3-3.4 Control Heads A suitable control unit, specifically Listed and Approved for use with the following electric control heads, shall be provided for supervision of the releasing circuits per NFPA requirements. In addition, a 24-hour back-up power source shall be provided per NFPA requirements.
  • Page 42: Electric Control Head, Stackable (Explosion Proof)

    0.2 continuous Electric Control Head, P/N 82-486500-010, is designed for installation directly on Kidde ECS System cylinder valves only. This control head must not be installed on any other type of HFC-227ea cylinder valve, nitrogen valve or carbon dioxide cylinder valve. Installation of this control head on any other...
  • Page 43: 3-3.4.2 Electric/Cable Operated Control Heads

    Component Description 3-3.4.2 Electric/Cable Operated Control Heads, P/N 81-895630-000 and P/N WK-897494-000 The electric/cable operated control head mounts directly on top of the HFC-227ea cylinder valve and provides for both electric actuation or remote cable operation. The control head is operated remotely by an electrical signal from a detection system or electric manual pull station.
  • Page 44: Cable Operated Control Head, P/N 81-979469-000

    Component Description 3-3.4.3 Cable Operated Control Head, P/N 81-979469-000 The Cable Operated Control Head is used for systems designed for manual operation only. It mounts directly on top of the HFC-227ea cylinder valve and is operated either remotely from a cable manual pull station or locally using the manual lever on the control head (see Figure 3-16).
  • Page 45: Lever Operated Control Head, P/N Wk-870652-000

    Component Description 3-3.4.4 Lever Operated Control Head, P/N WK-870652-000 The Lever Operated Control Head is equipped with an operating lever, secured in the closed position by a safety pull pin. By removing the safety pin, the lever can be manually rotated to the open position, thereby activating the cylinder or valve on which it is installed (see Figure 3-17).
  • Page 46: Lever/Pressure Operated Control Head, P/N 82-878751-000

    Component Description 3-3.4.5 Lever/Pressure Operated Control Head, P/N 82-878751-000 The Lever/Pressure Operated Control Head allows manual or pressure actuation of several system components, including HFC-227ea cylinder valves and nitrogen actuators (see Figure 3-18). ALLOW APPROX. 2 in. (50.8 mm) LEVER CLEARANCE FOR SAFETY PIN OPERATION OF LEVER...
  • Page 47: 3-3.4.6 Pressure Operated Control Head, P/N 82-878737-000 And

    Component Description 3-3.4.6 Pressure Operated Control Head, P/N 82-878737-000 and P/N 82-878750-000 The Pressure Operated Control Head, P/N 82-878737-000, allows for pressure actuation of HFC-227ea cylinders and is mounted directly on top of the HFC-227ea cylinder valve (see Figure 3-19). The pressure operated control head, P/N 82-878750-000, offers a stackable design and is used where an electric/mechanical control head actuation is also required on the same cylinder (see Figure 3-20).
  • Page 48: 3-3.5 Remote Pull Stations

    Component Description 3-3.5 Remote Pull Stations 3-3.5.1 Electric Remote Pull Box, P/N 84-330001-001 The Electric Remote Pull Box is an electrically operated device. To actuate the HFC-227ea system, pull the handle on the front of the box. 3-3.5.2 Cable Manual Pull Station, Surface, P/N 81-871403-000 The surface type remote Cable Manual Pull Station is a cable operated device.
  • Page 49: Actuation Accessories

    Component Description 3-3.6 Actuation Accessories 3-3.6.1 Nitrogen Actuator, Mounting Bracket and Adapter, P/N WK-877940-000, P/N WK-877845-000 and P/N WK-699205-010 respectively Gas pressure from a nitrogen cylinder is routed to the pressure operated control head mounted on each HFC-227ea cylinder. When the control head on the remote nitrogen cylinder is actuated, the HFC-227ea cylinder will be activated, causing HFC-227ea to be discharged from the cylinder.
  • Page 50: Flexible Actuation Hose, P/N Wk-264986-000 And P/N Wk-264987-000

    Component Description 3-3.6.2 Flexible Actuation Hose, P/N WK-264986-000 and P/N WK-264987-000 The Flexible Actuation Hose is used in multiple cylinder systems. Pilot pressure is directed to a pressure operated control head on each HFC-227ea cylinder valve using a 1/4-inch actuation hose (see Figure 3-23 and Table 3-12).
  • Page 51: 3-3.6.4 Tees, Elbows And Adapters

    Component Description 3-3.6.4 Tees, Elbows and Adapters Tees, elbows and adapters connect actuation hoses to pressure operated control heads in multiple cylinder system installations (see Figure 3-25). MALE CONNECTOR 1/8 in. NPT X 5/16 in. TUBING P/N WK-699205-010 MALE ELBOW MALE BRANCH TEE 1/8 in.
  • Page 52: Valve Outlet Adapters, P/N Wk-283904-000, P/N Wk-283905-000 And P/Nwk-283906-000

    Component Description 3-3.7.2 Valve Outlet Adapters, P/N WK-283904-000, P/N WK-283905-000 and P/N WK-283906-000 A valve outlet adapter connects the cylinder valve outlet to the discharge piping when a flexible discharge hose is not used (see Figure 3-27 and Table 3-14). Note: 3"...
  • Page 53: Manifold El-Checks, P/N Wk-877690-000 And P/N 82-878743-000

    Component Description 3-3.7.4 Manifold EL-Checks, P/N WK-877690-000 and P/N 82-878743-000 Manifold El-Checks are installed at the discharge manifold in a multiple cylinder arrangement to allow removal of any HFC-227ea cylinder from the manifold while still retaining a closed system. The 2-inch El-check is used on the 10 through 350 lb size cylinders; the 2½-inch El- check is used with the 600 lb size cylinder (see Figure 3-29 and Table 3-15 and Table 3-16).
  • Page 54: Pressure Operated Switches, P/N 81-486536-000 And P/N 81-981332-000

    Component Description 3-3.7.5 Pressure Operated Switches, P/N 81-486536-000 and P/N 81-981332-000 Pressure Switches operate from system pressure upon discharge to energize or de-energize electrically operated equipment. Pressure switches may be used to shut down machinery and ventilation or to annunciate system discharge (see Figure 3-30 and Figure 3-31). OPERATED STEM SHOWN IN SET POSITION- PULL UP ON STEM TO MANUALLY...
  • Page 55: Pressure Operated Trip, P/N 81-874290-000

    Component Description 3-3.7.6 Pressure Operated Trip, P/N 81-874290-000 Pressure Operated Trips are used to close off the hazard space upon system discharge. The trips, operated by system pressure, are designed to release self-closing units for doors, windows and dampers. The maximum load to be attached to a pressure trip is 100 lb (45.36 kg).
  • Page 56: Corner Pulleys, P/N 81-803808-000 And P/N Wk-844648-000

    Component Description 3-3.7.8 Corner Pulleys, P/N 81-803808-000 and P/N WK-844648-000 Corner Pulleys change the direction of cable lines without binding to ensure smooth operation. P/N 81-803808-000 is used for all watertight applications; P/N WK-844648-000 is used for all industrial applications (see Figure 3-33 and Figure 3-34). 1.75"...
  • Page 57: Cylinder Supervisory Pressure Switch, P/N 06-118262-001

    Component Description 3-3.7.9 Cylinder Supervisory Pressure Switch, P/N 06-118262-001 The Cylinder Supervisory Pressure Switch, P/N 06-118262-001, is intended to detect a fall in pressure in the HFC-227ea cylinder (see Figure 3-35). The cylinder supervisory pressure switch can be wired for either normally-open or normally-closed operation, depending on installation requirements.
  • Page 58: 3-3.7.10 Supervisory Pressure Switch, P/N 06-118263-001

    Component Description 3-3.7.10 Supervisory Pressure Switch, P/N 06-118263-001 Note: The cylinder supervisory pressure switch can be installed on 600 lb through 900 lb ca- pacity HFC-227ea cylinders with a 3" discharge valve manufactured prior to May 2013. Any valve produced after May 2013 must use P/N 06-118262-001 Cylinder Supervisory Pressure Switch.
  • Page 59: 3-3.7.11 Main-To-Reserve Transfer Switch, P/N 84-802398-000

    Component Description 3-3.7.11 Main-to-Reserve Transfer Switch, P/N 84-802398-000 The Main-to-Reserve Switch is installed on systems having main and reserve cylinders. Placing the switch in either the MAIN or RESERVE position provides uninterrupted fire protection during system maintenance or in the event of a system discharge (see Figure 3-37). ¾...
  • Page 60: 3-3.7.12 Discharge Nozzles

    Component Description 3-3.7.12 Discharge Nozzles The 180° and 360° discharge nozzles are designed to provide the proper flow rate and distribution of HFC-227ea to flood a hazard area. The 180° nozzle is engineered to provide a 180° discharge pattern for sidewall applications. The 360° nozzle offers a full 360° discharge pattern for installations where nozzles are located in the center of the hazard.
  • Page 61: 3-3.8 Other Accessories

    Component Description 3-3.8 Other Accessories 3-3.8.1 Hydrostatic Test Adapters The hydrostatic pressure test adapter is installed on the HFC-227ea cylinder in place of the cylinder valve when the cylinder is to be hydrostatically pressure tested. For cylinder test requirements, see Paragraph 5-5.3 of this manual. 3-3.8.2 HFC-227ea Cylinder Recharge Adapters The HFC-227ea recharge adapter is installed in the cylinder discharge outlet during the cylinder...
  • Page 62: 3-3.8.3 Cylinder Seating Adapter (P/N Wk-933537-000)

    Component Description 3-3.8.3 Cylinder Seating Adapter (P/N WK-933537-000) The HFC-227ea Seating Adapter is installed on the cylinder actuation port during the cylinder charging procedure. This adapter is used for seating the valve assembly after charging and super pressurization is complete. This seating adapter can be used for the Agent or Nitrogen Pilot cylinders.
  • Page 63 Component Description THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 3-36 06-236115-001...
  • Page 64: Design And Installation

    Design and Installation CHAPTER 4 DESIGN AND INSTALLATION INTRODUCTION This chapter is intended for system designers and installers. It outlines the steps needed to design the system including the limitations imposed on the design by the system hardware. The second part of this chapter explains equipment installation. DESIGN PROCEDURE 4-2.1 General...
  • Page 65: 4-2.2.1 Determine Minimum Use Concentration Required

    Design and Installation 4-2.2.1 Determine Minimum Use Concentration Required A Class A surface fire hazard is one that involves ordinary combustible materials. A Class B fire hazard is one that involves flammable and combustible liquids and flammable gasses. A Class C fire hazard is one that involves energized electrical equipment. Table 4-1 shows the minimum design concentrations of HFC-227ea for Class A surface fires and Class C fires.
  • Page 66: 4-2.2.2.1 Adjusting For Altitude Or Pressure

    Design and Installation 4-2.2.2.1 Adjusting for Altitude or Pressure The procedure for determination of the agent quantity assumes that the protected enclosure is at sea level or has an internal pressure of 14.7 psia (101.4 kPa). The design agent quantity must be adjusted where the protected enclosure is at an altitude or pressure that differs by more than 11% from sea level values.
  • Page 67: Class B Suppression Design Concentrations

    Design and Installation Table 4-3. Class B Suppression Design Concentrations Design Design Concentration, Concentration, 30% Cup Burner Fuel Burner Fuel 30% Safety Factor Safety Factor (% v/v) (% v/v) (%v/v) (%v/v) Acetone 1-Hexene Acetonitrile Hydraulic Fluid* t-Amyl Alcohol Hydraulic Oil* AV Gas Hydrogen 13.2...
  • Page 68: Hfc-227Ea Total Flooding Concentration Factors (W/V), English

    Design and Installation Table 4-4. HFC-227ea Total Flooding Concentration Factors (W/V), English Specific Weight Requirements of Hazard Volume, W V  (lb/ft Temp Vapor Design Concentrations (% by Volume) Volume (°F) 6.25 6.70 /lb) 2.0210 0.0316 0.0330 0.0355 0.0372 0.0430 0.0489 0.0550 0.0612...
  • Page 69: Hfc-227Ea Total Flooding Concentration Factors (W/V), Metric

    Design and Installation Table 4-5. HFC-227ea Total Flooding Concentration Factors (W/V), Metric Specific Weight Requirements of Hazard Volume, W V  (kg/m Temp Vapor Design Concentrations (% by Volume) Volume (°C) /kg) 6.25 6.70 0.1268 0.5258 0.5659 0.5936 0.6858 0.7800 0.8763 0.9748 1.0755...
  • Page 70: Determine What Components Are Required

    Design and Installation 4-2.2.3 Determine What Components are Required • Cylinder size, quantity and fill requirements. Refer to Table 4-4 and Table 4-5. • Cylinder framing, mounting brackets, etc. • Detection and control equipment required. • Other system requirements, such as reserve supply, pressure switches, etc. 4-2.2.4 Locate Nozzles Locate nozzles based on the following:...
  • Page 71: 4-2.2.8 Using The Hfc-227Ea Concentration Flooding Factors

    Design and Installation 4-2.2.8 Using the HFC-227ea Concentration Flooding Factors To find the total quantity of HFC-227ea required at a specific temperature and concentration, multiply the hazard area volume by the multiplier from Table 4-4 and Table 4-5 that correspond to the design temperature and concentration desired. Note: NFPA 2001, 2012 Edition and the U.S.
  • Page 72: 4-2.3 Design Criteria

    The latest version of the flow calculation software program is the only calculation method to be used with Kidde ECS System equipment. No other CAUTION calculation method is accepted by Kidde.
  • Page 73 Design and Installation BULL TEE FLOW BULL TEE FLOW BULL TEE SPLIT LIMITS SPLIT LIMITS OUT - 50% OUT - 50% OUT - 70% OUT - 30% BULL TEE BULL TEE MINIMUM MAXIMUM UNBALANCE UNBALANCE IN - 100% IN - 100% SIDE TEE FLOW SIDE TEE FLOW SIDE TEE...
  • Page 74: Tee Flow Splits

    Design and Installation 4-2.3.2 Tee Flow Splits Flow splits at tee junctions are sensitive to gravity. Even though turbulent flow exists, there is a tendency for the vapor phase to migrate to the upper portion of the pipe leaving a more dense medium at the bottom of the pipe.
  • Page 75: 4-2.3.4 Nozzle Selection And Placement

    Design and Installation 4-2.3.4 Nozzle Selection and Placement There are two basic Kidde ECS System nozzle configurations: 1. The 360° nozzle, which provides a full 360° discharge pattern designed for placement in the center of the hazard. 2. The 180° nozzle, which provides a 180° discharge pattern designed for placement adjacent to a side wall of the hazard.
  • Page 76: 4-2.3.5.1 Limits On Nozzle Conditions

    Design and Installation • 180° Nozzles-180° nozzles must be located 12 +/- 2 inches (0.3 +/- 0.05 m) from a wall, with the orifices directed away from the wall. The nozzle shall be located as close to the center of the wall as possible, but at least 1/3 of the way along the wall. 180°...
  • Page 77: 4-2.3.6 Pipe Sizing

    Design and Installation System With A System With A System With Ceiling Single Row of Nozzles Multiple Row of Nozzles and Subfloor Nozzles 30 ft. Max 30ft. Max 30 ft. Max Figure 4-4. Nozzle Limitations Note: Any system designed for a space less than 12 in (0.3 m) in height is not a UL Listed or FM Approved design.
  • Page 78: Other Conditions

    4-2.4.2 Storage Temperature Kidde ECS System equipment is suitable for storage from 32°F to 130°F (0°C to 54°C). 4-2.4.3 System Operating Pressure The normal system operating pressure for Kidde ECS System equipment is 360 PSIG at 70°F (25 bar gauge at 21°C).
  • Page 79: 4-2.5.1 Cylinders Close Coupled Using Pressure From A Master Cylinder

    Design and Installation 4-2.5.1 Cylinders Close Coupled Using Pressure From A Master Cylinder For cylinders close coupled (reach of one flex hose, max. 30 in) using pressure from one master HFC-227ea cylinder, a maximum of fourteen slave cylinders close coupled can be actuated from that one master cylinder, using pressure operated control heads on the slave cylinders.
  • Page 80: 4-2.5.3 Cylinders Not Close Coupled Using Pilot Nitrogen Cylinder Pressure

    Design and Installation 4-2.5.3 Cylinders Not Close Coupled Using Pilot Nitrogen Cylinder Pressure For cylinders not close coupled using nitrogen pressure from one pilot nitrogen cylinder, from one to fifteen slave HFC-227ea cylinders can be actuated from the one pilot nitrogen cylinder using pressure operated control heads on the slave cylinders.
  • Page 81: 4-2.5.4 Cylinders Close Coupled Using Pilot Nitrogen Pressure

    P/N WK-699205-010 1/4” SCH. 40 PIPE ACTUATION HOSE 320 FT. MAX. ACTUATION HOSE PIPE LENGTH Figure 4-8. Pressure Actuation Using Pressure from 1 Cylinder to Actuate a Maximum of Fifteen Sets of ECS Cylinders, Close Coupled. October 2014 4-18 06-236115-001...
  • Page 82: 4-2.5.5 Corner Pulley And Cable Limitations

    4-3.1 General All Kidde ECS System equipment must be installed to facilitate proper inspection, testing, manual operation, recharging and any other required maintenance as may be necessary. Equipment must not be subject to severe weather conditions or mechanical, chemical or other damage that could render the equipment inoperative.
  • Page 83: 4-3.2.2.1 Ferrous Piping

    Design and Installation 4-3.2.2.1 Ferrous Piping Black steel or galvanized pipe must be either ASTM A-53 seamless or electric resistance welded, Grade A or B, or ASTM A-53 furnace weld Class F (up to 1½” diameter) or ASTM A- 106, Grade A, B or C. ASTM B-120 and ordinary cast iron pipe must not be used. The thickness of the pipe wall must be calculated in accordance with ANSI B-31.1, Power Piping Code.
  • Page 84: 4-3.3 Installation Of Pipe And Fittings

    Design and Installation 4-3.3 Installation of Pipe and Fittings Pipe and fittings must be installed in strict accordance with the system drawings and good commercial practices. The piping between the cylinder and the nozzles must be the shortest route possible, with a minimum of fittings. Any deviations in the routing or number of fittings must be approved by the design engineer before installation.
  • Page 85: 4-3.7 Installation Of Valve Outlet Adapter

    Design and Installation 4-3.7 Installation of Valve Outlet Adapter Always connect a valve outlet adapter into system piping (union connection) before connecting to an HFC-227ea cylinder. WARNING Install valve outlet adapter (P/Ns WK-283904-000, WK-283905-000, and WK-283906-000) in system piping. Tighten securely and continue with threaded rigid pipe. A union needs to be installed for ease of disconnecting the cylinder.
  • Page 86: Installation Of The Flexible Hose Directly Into System Piping, English (Inches)

    Design and Installation Table 4-9. Installation of the Flexible Hose Directly into System Piping, English (inches) Dimensions in inches Cylinder Capacity 10 lb 14 5/8 16 3/4 1 1/2 20 lb 14 5/8 16 3/4 1 1/2 40 lb 14 5/8 16 3/4 1 1/2 70 lb...
  • Page 87: Installation Of Master Cylinder Adapter Kit P/N 82-894895-000

    Design and Installation 4-3.9 Installation of Master Cylinder Adapter Kit P/N 82-894895-000 Note: Master cylinder adapter installation can be accomplished safely with a pressurized cyl- inder. 1. Remove the 1/4-inch pipe plug from the slave actuation port on the master cylinder valve. ®...
  • Page 88: 4-3.10.1 Single Cylinder System

    Design and Installation 4-3.10.1 Single Cylinder System Cylinders must be located and mounted where they will not be accidently damaged or moved. If necessary, install suitable protection to prevent the WARNING cylinder from damage or movement. 1. Position HFC-227ea cylinder in designated location and secure in place with cylinder strap and attaching hardware (see Figure 4-11 and Table 4-11, through Table 4-12).
  • Page 89: Single Cylinder Installation Dimensions, English (Inches)

    Design and Installation Table 4-11. Single Cylinder Installation Dimensions, English (inches) Cylinder P/N 90-10001X-001 9.62 7.19 7.07 8.52 7.38 90-10002X-001 9.62 7.19 7.07 8.52 12.50 90-10004X-001 11.69 9.13 9.00 10.69 10.63 90-10007X-001 11.69 9.13 9.00 10.69 27.50 90-100121-001 16.18 12.94 12.75 14.56 23.75...
  • Page 90: 4-3.10.2 Multiple Cylinder System

    Design and Installation Table 4-13. Strap Part Numbers for Cylinder Installation Strap Part Number Cylinder Size WK-283945-000 10 and 20 lb WK-283934-000 40 and 70 lb WK-292971-000 125 and 200 lb (old style) 06-235317-001 125 and 200 lb (new style) WK-281866-000 350 lb WK-294651-000...
  • Page 91: Multiple Cylinder Installation Dimensions, Inches

    Design and Installation ANCHOR AND STUD (TYP) (TYP) WALL FRAMING CYLINDER SUPPORT CYLINDER (TYP) CYLINDER (BOLT SIZE) STRAP FLOOR VERSABAR LEVEL Figure 4-12. Multiple Cylinder Installation, Vertical Mounting (see Table 4-14 and Table 4-15 for dimensions) Table 4-14. Multiple Cylinder Installation Dimensions, Inches Dimensions Cylinder Part Number 90-10001X-001...
  • Page 92: 4-3.10.3 Main And Reserve System

    Design and Installation Table 4-15. Multiple Cylinder Installation Dimensions, Millimeters Dimensions Cylinder Part Number 90-10001X-001 90-10002X-001 90-10004X-001 90-10007X-001 90-100125-001 90-10020X-001 90-10020X-101 90-10035X-001 90-10060X-001 90-10060X-100 90-10090X-001 1232 4-3.10.3 Main and Reserve System Install main and reserve systems as instructed in the previous paragraphs. 4-3.11 Installation of Electric Control Heads Before installing a control head on an HFC-227ea cylinder valve, ensure the...
  • Page 93 Design and Installation 2.90 in. (73.66 mm) 1.25-18 UNEF-2A CONNECTION ½ in.-14 NPT CONDUIT CONNECTION (134.11 mm) 5.28 in. (3) 18 AWG-LEADS 18 in. (457.2 mm) LONG SWIVEL NUT 1.25 - 18 UNEF - 2B CONNECTION Figure 4-13. Installation of Electric Control Head (Stackable Type), P/N 486500-01 0.750 NPT TO FLEXIBLE CONDUIT ADAPTER FLEXIBLE CONDUIT...
  • Page 94: Installation Of Pressure Operated Control Head, P/N 82-878751-000

    Design and Installation 4-3.12 Installation of Pressure Operated Control Head, P/N 82-878751-000 1. Remove the protection cap from the cylinder actuation port (see Figure 4-15). When attaching the Lever/Pressure operated control head to the valve, the swivel nut must be tightened to a toque of 55ft·lb. Failure to tighten the swivel WARNING nut may result in leakage during actuation.
  • Page 95: 4-3.13 Installation Of Electric/Cable Operated Control Head

    Design and Installation 4-3.13 Installation of Electric/Cable Operated Control Head, P/N 81-895630-000 and P/N WK-897494-000 The following procedures must be performed before attaching a control head to a cylinder valve. See Figure 4-16. 1/16 in. CABLE FLEXIBLE CONDUIT ½ in. E.M.T. 3/4 in.
  • Page 96: Installation Of Cable Operated Control Head, P/N 81-979469-000

    Design and Installation 4-3.14 Installation of Cable Operated Control Head, P/N 81-979469-000 The cable operated control head (P/N 81-979469-000) must not be used with the stackable pressure operated control head (P/N 82-878750-000). Installing the cable operated control head on the actuation port of the stackable pressure WARNING operated control head will cause the device to malfunction.
  • Page 97: 4-3.16 Installation Of Nitrogen Cylinder, P/N Wk-877940-000 And Mounting Bracket, P/N Wk-877845-000

    Design and Installation 4-3.16 Installation of Nitrogen Cylinder, P/N WK-877940-000 and Mounting Bracket, P/N WK-877845-000 1. Locate the nitrogen cylinder mounting bracket in an area where the cylinder valve assembly and control head will be protected from inclement weather by a suitable total or partial en- closure, preferably adjacent to the HFC-227ea storage cylinders.
  • Page 98: Installation Of Pressure Trip, P/N 81-874290-000

    Design and Installation 4-3.18 Installation of Pressure Trip, P/N 81-874290-000 Install the pressure trip on the discharge manifold or piping in the horizontal position as shown on the system drawings. Connect the trip to the piping with 1/2-inch Schedule 40 pipe. The minimum operating pressure required is 75 PSIG (5 bar gauge).
  • Page 99: 4-3.21 Installation Of Supervisory Pressure Switch (P/Ns 06-118262-001 And 06-118263-001)

    FOR SWITCH CONNECTION Figure 4-17. Installation of Supervisory Pressure Switch (Up to 2½ in Valve) Note: The control panel must be UL Listed and/or FM Approved for releasing device service and compatible with Kidde ECS System equipment. October 2014 4-36 06-236115-001...
  • Page 100 Design and Installation BLUE: N.O. (N.C. UNDER PRESSURE) BLACK: N.C. (N.O. UNDER PRESSURE) VIOLET: COM. FACTORY SEALED LEADWIRES 36 in. LONG ± 1 in. 0.500 -14 NPT CAUTION LABEL NAMEPLATE LABEL 4.125 in. (10.48 cm) O-RING 0.250 in. SAE 45° FLARE (CONNECTION FOR 06-118262-001 SHOWN)
  • Page 101: 4-3.21.1 Installation Of Pressure Switch 06-118262-001

    Design and Installation 4-3.21.1 Installation of Pressure Switch 06-118262-001 Install the pressure switch as follows: Note: Do not use with 3" valves manufactured prior to May 1, 2013. 1. Check that the sealing surface of the flare connection of the supervisory switch is not scratched, dented, scored, etc.
  • Page 102: 4-3.22 Post-Installation Checkout

    Design and Installation 4-3.22 Post-Installation Checkout After an HFC-227ea system installation has been completed, perform the following inspections and tests. 1. Verify that the cylinders of correct weight and pressure are installed in accordance with in- stallation drawings. 2. Verify that the cylinder brackets and straps are properly installed and all fittings are tight. 3.
  • Page 103 Design and Installation THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 4-40 06-236115-001...
  • Page 104: Chapter 5 Maintenance

    Maintenance CHAPTER 5 MAINTENANCE INTRODUCTION This chapter contains maintenance instructions for the Kidde ECS System. These procedures must be performed regularly in accordance with regulations. If problems arise, corrective action must be taken. MAINTENANCE PROCEDURES HFC-227ea and nitrogen cylinder valve assemblies must be handled, installed,...
  • Page 105: Preventative Maintenance

    Maintenance PREVENTATIVE MAINTENANCE Perform preventive maintenance per Table 5-1. Table 5-1. Preventive Maintenance Schedule Schedule Requirement Paragraph Daily HFC-227ea 5-4.1 Check cylinder pressures Check Nitrogen cylinder pressures Monthly Inspect hazard area system components 5-4.2 Semi-Annually Test pressure switches 5-4.3 Test electric control heads Check HFC-227ea cylinder weights and pressures Every 2 Years Blow out distribution piping...
  • Page 106: Inspect Hoses

    Maintenance 5-4.2.3 Inspect hoses Inspect 1/4-inch flexible actuation hoses for loose fittings, damaged threads, cracks, distortion, cuts, dirt and frayed wire braid. Tighten loose fittings and replace hoses with stripped threads or other damage. If necessary, clean parts as directed in Paragraph 5-6.1. Inspect the adapters, couplings and tees at the HFC-227ea cylinder pilot outlets and tighten couplings if necessary.
  • Page 107: 5-4.2.10 Inspect Discharge Nozzles

    Maintenance 5-4.2.10 Inspect Discharge Nozzles Inspect discharge nozzles for dirt and physical damage. Replace damaged nozzles. If nozzles are dirty or clogged, refer to Paragraph 5-6.1. Nozzles must never be painted. Nozzles must be replaced by nozzles of the same part number. (A part number is located on each nozzle.) Nozzles must never be interchanged since random CAUTION interchanging of nozzles could adversely affect proper HFC-227ea distribution...
  • Page 108: 5-4.3.2 Electric Control Head Test

    Maintenance 5-4.3.2 Electric Control Head Test Electric control heads must be tested semiannually for proper operation. This test can be performed without discharging the HFC-227ea cylinders. Test one hazard area at a time before proceeding to the next, as follows: All control heads must be removed from HFC-227ea cylinders and nitrogen pilot cylinders prior to testing to prevent accidental cylinder discharge.
  • Page 109: 5-4.3.3 Check Hfc-227Ea Cylinder Weights And Pressures

    Maintenance 5-4.3.3 Check HFC-227ea cylinder weights and pressures Use the following procedures to check the weights and pressures of all HFC-227ea cylinders. 5-4.3.3.1 Cylinders Not Equipped with Flexible Tape Liquid Level Indicator Weigh 10 through 900 lb HFC-227ea cylinders as follows: Install a protection cap on the HFC-227ea cylinder valve actuation port and safety cap on the cylinder valve outlet port.
  • Page 110 Maintenance GRADUATED TAPE SHOWN IN MAGNETIC INTERLOCK POSITION READY TO TAKE READING TAKEN AT TOP READING. EDGE OF FITTING O-RING BRASS TUBE TAPE INSIDE HFC-227ea BRASS TUBE CYLINDER HFC-227ea MAGNETIC END OF LIQUID LEVEL TAPE ENGAGES IN MAGNETIC FIELD OF FLOAT WHEN TAPE IS PULLED UP TO TAKE READING.
  • Page 111 Maintenance 25.0 130°F 20.0 100°F 70°F 30°F 15.0 10.0 HFC-227ea Weight (lb.) Figure 5-2. Calibration Chart 125lb Cylinder 30.0 130°F 100°F 28.0 70°F 26.0 40°F 24.0 22.0 20.0 18.0 16.0 14.0 12.0 HFC-227ea Weight (lb.) Figure 5-3. Calibration Chart for Old 200lb Cylinder October 2014 06-236115-001...
  • Page 112 Maintenance 35.0 130°F 30.0 100°F 70°F 30°F 25.0 20.0 15.0 10.0 HFC-227ea Weight (lb.) Figure 5-4. Calibration Chart for a New 200lb Cylinder (New Design Ellipsoidal Head Manufactured After 3/98) 130°F 30.0 100°F 70°F 25.0 30°F 20.0 15.0 10.0 HFC-227ea Weight (lb.) Figure 5-5.
  • Page 113 Maintenance 130°F 30.0 100°F 70°F 25.0 30°F 20.0 15.0 10.0 HFC-227ea Weight (lb.) Figure 5-6. Calibration Chart for 600lb Cylinder 130°F (54°C) 100°F (38°C) 70°F (21°C) 30°F (-1°C) HFC-227ea Weight (lb.) Figure 5-7. Calibration Chart for 900lb Cylinder October 2014 5-10 06-236115-001...
  • Page 114: 5-4.4 Inspection Procedures-2 Year

    HFC-227ea. CAUTION All Kidde ECS cylinders are designed, fabricated, and factory tested at 1000 PSIG (68.9 bar gauge) in compliance with DOT CFR 49 4BA-500 or 4BW-500 as stamped on each cylinder. Two sets of regulations will apply to periodic inspection and test procedures depending on the following: 5-5.1...
  • Page 115: 5-5.3 Retest

    Maintenance 5-5.3 Retest DOT 4BA and 4BW cylinders used exclusively in HFC-227ea services that are commercially free from corroding components are required to be hydrostatically retested and restamped every five years, in accordance with the , prior to DOT Regulatory Compliance Guide, 49 CFR 180.209 recharge and shipment.
  • Page 116: 5-6.3 Repairs

    Maintenance 5-6.3 Repairs Replace all damaged parts found during inspection. Replacement procedures for HFC-227ea cylinders are provided below. Since replacement for other system components are similar, refer to the installation drawings and HFC-227ea system assembly drawings for guidance. HFC-227ea cylinders must be recharged when the cylinder pressure gauge indicates the pressure is below normal (360 PSIG at 70°F [25 bar gauge at 21°C]), immediately after discharge, when a loss in weight is in excess of 5% of the original charged net weight or when there is a loss of pressure (adjusted for temperature) of more than 10%.
  • Page 117: 5-7.2 Multiple Cylinder System

    Maintenance 5-7.2 Multiple Cylinder System Remove all control heads from the HFC-227ea cylinders. WARNING 1. Remove the supervisory pressure switches (where installed) by disconnecting the electrical connection at the switch, then remove the wire lead protection or conduit. Unscrew the switch from the cylinder valve and install the protection cap on the switch connection port.
  • Page 118: Reinstalling An Hfc-227Ea Cylinder

    Maintenance REINSTALLING AN HFC-227ea CYLINDER Installing an HFC-227ea Cylinder. Install HFC-227ea cylinders as follows: 5-8.1 Single Cylinder System 1. Position the HFC-227ea cylinder in the designated location. Secure it in place with a cylinder strap or wall bracket and mounting hardware. Orient the cylinder with the valve outlet an- gled toward the cylinder discharge piping (refer to the installation drawings).
  • Page 119: 5-8.3 Nitrogen Pilot Cylinders

    Maintenance 5-8.3 Nitrogen Pilot Cylinders 1. Install nitrogen cylinder in mounting bracket. Rotate cylinder until valve outlet is in desired position. 2. Tighten mounting bracket strap. 3. Remove pipe plug and connect adapter (Part No. WK-699205-010) to cylinder valve outlet port.
  • Page 120: Chapter 6 Post- Discharge Maintenance

    Post-Discharge Maintenance CHAPTER 6 POST- DISCHARGE MAINTENANCE INTRODUCTION Follow these procedures after the Kidde ECS System has been activated and HFC-227ea has been discharged. POST-FIRE MAINTENANCE 6-2.1 HFC-227ea Valve Inspection and Service Inspect and service the HFC-227ea valve as follows: Important–Because the HFC-227ea tends to dissolve and wash out lubricant, certain...
  • Page 121: Valve Components

    Post-Discharge Maintenance GAGING DIMENSIONS VALVE CORE 0.515/0.565 VALVE CAP O-RING CAP SPRING O-RING, PISTON, SAFETY BACK-UP RING (See enlarged view in Figure 6-2.) PISTON O-RING SEAT SEAT RETAINER O-RING, NECK SIPHON TUBE Figure 6-1. Valve Assembly (1 1/2”, 2”, and 2 1/2”) O-RING, PISTON TEFLON BACK-UP RING...
  • Page 122: 6-2.3 Valve Disassembly (3-Inch Valve)

    Post-Discharge Maintenance 6-2.3 Valve Disassembly (3-inch Valve) Note: Refer to Figure 6-3 and Table 6-3 for items. Before removing the valve, make sure that all pressure has been relieved from the cylinder. To relieve any remaining pressure, ensure the cylinder is secured WARNING then depress the pressure check in the Supervisory Pressure Switch.
  • Page 123: 6-2.4 Replacing 3-Inch Valve Pilot Check

    Post-Discharge Maintenance 6-2.4 Replacing 3-Inch Valve Pilot Check Note: Refer to Figure 6-4 for items. 1. Remove the valve cap. 2. Using retaining ring pliers, remove the retaining ring holding the pilot check, spring, and disk in place. Save the retaining ring. 3.
  • Page 124: Valve Assembly (3-Inch)

    Post-Discharge Maintenance 6-2.6 Valve Assembly (3-inch) Note: Refer to Figure 6-3 and Table 6-3. If the siphon tube is being replaced due to damage or wear, contact Kidde Fenwal Inc. to ensure the proper replacement part is ordered based on the CAUTION manufacturing date of the valve.
  • Page 125 Post-Discharge Maintenance Never install any type disc other than specified in Table 6-4 for the appropriate cylinder. Installing the incorrect disc could result in violent rupture of the cylinder and serious injury. Make sure that multiple safety discs are not stuck together. Installing more than one safety disc could result in violent rupture of the cylinder and serious WARNING injury.
  • Page 126: Safety Disc Replacement Table (3-Inch Valve And New 2-Inch Valve)

    Post-Discharge Maintenance 6-2.8 Safety Disc Replacement (3-inch and 2-inch Manufactured after April 2014) Note: This process only applies to 3-inch valves and 2-inch valves manufactured after April 2014. For 2-inch valves manufactured during or before April 2014, see Section 6-2.7. Whenever the valve is rebuilt, the Safety Disc Assembly must be replaced.
  • Page 127: Recharging Hfc-227Ea Cylinders

    Post-Discharge Maintenance RECHARGING HFC-227ea CYLINDERS HFC-227ea cylinders may require retest before recharging. See Paragraph 5-5 for details on cylinder retest. FM Approval is based upon the usage of factory CAUTION filled HFC-227ea cylinders. Under no circumstances while performing either cylinder recharge or leak test should a charged cylinder be allowed to free stand without either the charging apparatus attached or the safety cap installed.
  • Page 128: 6-3.2 Charging System Diagram

    HFC-277ea Agent System Storage Container Cylinder 26 scale optional salvage connection Flexible Hose Figure 6-8. Typical HFC-227ea Charging System for Kidde ECS Cylinders Table 6-6. Item List for Figure 6-8 Item No. Description Item No. Description Item No. Description Item No.
  • Page 129: 6-3.3 Charging Procedure

    Charging Procedure Recharge HFC-227ea cylinder and valve assembly as follows: Note: HFC-227ea cylinder received from Kidde Fire Systems may be pressurized per the par- tial fill tag. 1. Check the cylinder for the last hydrostatic test date. Perform any required Department of Transportation (DOT) requalification tests or examinations.
  • Page 130: Pressure Vs. Temperature

    Post-Discharge Maintenance 15. Monitor the scale and record the empty cylinder assembly weight. Determine the charge weight using the formula C=A+B+N where A is the empty cylinder weight, B is the weight of the HFC-227ea agent indicated on the valve nameplate and N is the weight of the ni- trogen charge.
  • Page 131 Post-Discharge Maintenance Hissing or discharge coming from vent valve (Item 4) indicates the piston is not seated properly or has opened. If this occurs, repeat Step 23. Verify that CAUTION the cylinder valve piston remains closed. 25. Keep the vent valve (Item 4) open. Close valve (Item 5) and once again open valve (Item 6) to reapply nitrogen pressure to the actuation port.
  • Page 132: 6-3.4 Hfc-227Ea Cylinder Leak Test

    Post-Discharge Maintenance 6-3.4 HFC-227ea Cylinder Leak Test Clamp HFC-227ea cylinder securely in place. The clamping device and supports must be capable of withstanding a thrust force of 1800 lb (817 kg). This approximates the thrust force generated out of the HFC-227ea cylinder valve WARNING outlet on a full, wide open discharge.
  • Page 133: 6-3.5 Salvaging Hfc-227Ea From A Leaking Cylinder Assembly

    Post-Discharge Maintenance 6-3.5 Salvaging HFC-227ea from a Leaking Cylinder Assembly Target container must be significantly larger than the source container to prevent dangerous pressure buildup. WARNING 1. Close the HFC-227ea supply valve (Item 19) and close valve (Item 21). Open valve (Item 20) to vent pressure.
  • Page 134: Nitrogen Pilot Cylinder Service And Maintenance

    Post-Discharge Maintenance NITROGEN PILOT CYLINDER SERVICE AND MAINTENANCE Any area in which nitrogen is used or stored must be properly ventilated. A person working in an area where air has become enriched with nitrogen can become unconscious without sensing the lack of oxygen. Remove the victim to WARNING fresh air.
  • Page 135: 6-4.3 Nitrogen Cylinder Recharge

    Post-Discharge Maintenance 6-4.3 Nitrogen Cylinder Recharge Nitrogen cylinders must be recharged when the cylinder pressure gauge indicates pressure is below normal (1800 PSIG at 70°F [124 bar gauge at 21°C] or as adjusted for temperature) or immediately after discharge. Nitrogen used for charging must comply with Federal Specification BB-N-411C, Grade A, Type 1.
  • Page 136: Nitrogen Cylinder Installation

    Post-Discharge Maintenance 6-4.4 Nitrogen Cylinder Installation 1. Install the nitrogen cylinder in position in the mounting bracket. 2. Tighten sufficiently to hold cylinder in place while allowing cylinder enough free play to be manually rotated. 3. Turn the cylinder until the cylinder valve discharge outlet is in the desired position. The nitrogen cylinder must be positioned so that the control head, when installed, is readily accessible and cannot be obstructed during manual CAUTION...
  • Page 137 Post-Discharge Maintenance THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 6-18 06-236115-001...
  • Page 138: Introduction And Parts List

    PARTS LIST INTRODUCTION AND PARTS LIST The table below, and on the following pages, provides a complete list of the Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent parts and associated system equipment. Equipment can be ordered as complete assemblies or as individual items. In most situations, when ordering a system, it will be easier and more cost effective to order by assembly part numbers.
  • Page 139 Parts List Table 7-1. Parts List Nomenclature Part Number Original P/N Valve Outlet Adapters 10-125 lb. Cylinders WK-283904-000 283904 200-350 lb. Cylinders WK-283905-000 283905 600 lb. Cylinders (old style; before 9/01) WK-283906-000 283906 Cylinder Straps 10-20 lb WK-283945-000 283945 40-70 lb WK-283934-000 283934 125-200 lb (new style cylinder, after 3/98)
  • Page 140 Parts List Table 7-1. Parts List Nomenclature Part Number Original P/N Pressure Control Equipment Master Cylinder Adapter Kit 82-844895-000 844895 Male Branch Tee, 5/16 in Flare x 1/8 in NPT WK-699205-050 6992-0505 Male Elbow, 5/16 in Flare x 1/8 in NPT WK-699205-030 6992-0503 Male Connector, 5/16 in Flare x 1/8 in NPT...
  • Page 141 Parts List Table 7-1. Parts List Nomenclature Part Number Original P/N Check Valves Check Valve, 1/2 in NPT 81-800327-000 800327 Check Valve, 3/4 in NPT 81-800266-000 800266 Check Valve, 1 in NPT WK-800443-000 800443 Check Valve, 1-1/4 in NPT 81-800444-000 800444 Check Valves, 1-1/2 in NPT 81-870152-000...
  • Page 142 Parts List Table 7-1. Parts List Nomenclature Part Number Original P/N Safety Burst Disc Assemblies and Rebuild kits Assembly, 3" Valve Safety Burst Disc 90-170100-000 Assembly, 2" Valve Safety Burst Disc 90-150100-000 Kit, 2" Valve re-build. For valves manufactured prior to May 2014. 90-150100-000 Includes 1 of each of the following: WK-264925-000 - Safety Disc, 2"...
  • Page 143: Obsolete Parts

    Parts List OBSOLETE PARTS The following parts are no longer in service. For replacement options, contact your distributor or Kidde-Fenwal, Inc. Nomenclature Part Number Original P/N 10-125 lb Cylinders (old style supplied before 9/01) WK-283906-000 283906 125-200 lb (old style cylinder, before 3/98) WK-292971-000 292971 200 lb Cradle...
  • Page 144: Discharge Nozzles

    Parts List DISCHARGE NOZZLES Only listed Kidde ECS System HFC-227ea nozzles are to be used on Kidde ECS Systems. Failure to comply with this WARNING can result in unpredictable WARNING agent distribution. 7-3.1 UL Listed 360 Degree Nozzles Note: An additional nozzle finish has been added for a special application. This is a nickel plated nozzle designed to the specifications of the brass version which is FM Approved.
  • Page 145 Parts List UL Listed 360 Degree Nozzles Area (in 1/2 in NPT 3/4 in NPT 1 in NPT 1-1/4 in NPT 1-1/2 in NPT 2 in NPT 0.3927 90-194025-250 90-194026-250 0.4150 90-194025-257 90-194026-257 0.4280 90-194025-261 90-194026-261 0.4433 90-194025-266 90-194026-266 0.4649 90-194025-272 90-194026-272 0.4821...
  • Page 146: 7-3.2 Ul Listed 180 Degree Nozzles

    Parts List 7-3.2 UL Listed 180 Degree Nozzles: Note: An additional nozzle finish has been added for a special application. This is a nickel plated nozzle designed to the specifications of the brass version which is FM Approved. The part numbers are exact to that below except for the sixth digit which is a “3”...
  • Page 147: Parts List

    Parts List UL Listed 360 Degree Nozzles Area (in 1/2 in NPT 3/4 in NPT 1 in NPT 1-1/4 in NPT 1-1/2 in NPT 2 in NPT 0.4056 90-194015-250 90-194016-250 0.4233 90-194015-257 90-194016-257 0.4400 90-194015-261 90-194016-261 0.4485 90-194015-266 90-194016-266 0.4734 90-194015-272 90-194016-272 0.4954...
  • Page 148 APPENDIX A MATERIAL SAFETY DATASHEETS P/N 06-236115-001 October 2014...
  • Page 149 IDENTIFICATION OF THE SUBSTANCE/PREPARATIONS AND OF THE COMPANY UNDERTAKING Product Name FM-200 (Fire Extinguishing Agent) Other Trade Names Heptafluoropropane, HFC-227ea Fire Extinguishing Agent Product Description Manufacturer/Supplier Kidde Fire Systems Address 400 Main Street Ashland, MA 01721 Phone Number (508) 881-2000 (800) 424-9300 Chemtrec Number...
  • Page 150 MATERIAL SAFETY DATA SHEET FM-200 (Fire Extinguishing Agent) FIRST AID MEASURES Eyes Immediately flood the eye with plenty of warm water for at least 15 minutes , holding the eye open. Obtain medical attention if soreness or redness persists. Skin Flush with water.
  • Page 151 MATERIAL SAFETY DATA SHEET FM-200 (Fire Extinguishing Agent) EXPOSURE CONTROLS/PERSONAL PROTECTION Engineering Control Measures Use with adequate ventilation. There should be local procedures for the selection, training, inspection and maintenance of this equipment. When used in large volumes or odor becomes apparent, use local exhaust ventilation.
  • Page 152 MATERIAL SAFETY DATA SHEET FM-200 (Fire Extinguishing Agent) TOXICOLOGICAL INFORMATION Acute Toxicity 4 hour LC50(rat) >788,698 ppm Chronic Toxicity/Carcinogenicity This product is not expected to cause long term adverse health effects. Genotoxicity This product is not expected to cause any mutagenic effects. Tests have shown that this material does not cause genetic damage in bacterial or mammalian cell cultures.
  • Page 153 MATERIAL SAFETY DATA SHEET FM-200 (Fire Extinguishing Agent) REGULATORY INFORMATION US REGULATIONS (Federal, State) and INTERNATIONAL CHEMICAL REGISTRATION LAWS TSCA Listing This product contains ingredients that are listed on or exempt from listing on the EPA Toxic Substance Control Act Chemical Substance Inventory. EINECS Listing All ingredients in this product are listed on the European Inventory of Existing Commercial Chemical Substances (EINECS) or the European List of New Chemical Substances (ELINCS) or are exempt from...
  • Page 154 It is the user's responsibility to satisfy himself as to the suitability and completeness of such information for its own particular use. Kidde Fire Systems assumes no responsibility for personal injury or property damage resulting from use, handling or from contact with this product.
  • Page 155 Nitrogen (Expellant) IDENTIFICATION OF THE SUBSTANCE/PREPARATIONS AND OF THE COMPANY UNDERTAKING Product Name Nitrogen (Expellant) Other Trade Names Product Description Expellant Manufacturer/Supplier Kidde Fire Systems 400 Main Street Address Ashland, MA 01721 (508) 881-2000 Phone Number Chemtrec Number (800) 424-9300...
  • Page 156 MATERIAL SAFETY DATA SHEET Nitrogen (Expellant) FIRST AID MEASURES Eyes No specific measures. Skin No specific measures. Ingestion Ingestion is not considered a potential route of exposure. Inhalation Remove from exposure. If there is difficulty in breathing, give oxygen. Obtain medical attention immediately.
  • Page 157 MATERIAL SAFETY DATA SHEET Nitrogen (Expellant) EXPOSURE CONTROLS/PERSONAL PROTECTION Respiratory Protection Not normally required. In oxygen deficient atmospheres, use a self contained breathing apparatus, as an air purifying respirator will not provide protection. Hand Protection Use leather or sturdy work gloves when handling cylinders. Eye Protection Chemical goggles or safety glasses with side shields.
  • Page 158 MATERIAL SAFETY DATA SHEET Nitrogen (Expellant) TOXICOLOGICAL INFORMATION Genotoxicity This product is not expected to cause any mutagenic effects. Reproductive/Developmental Toxicity This product is not expected to cause adverse reproductive effects. ECOLOGICAL INFORMATION Mobility Nitrogen occurs naturally in the atmosphere. Persistence/Degradability Nitrogen occurs naturally in the atmosphere.
  • Page 159 MATERIAL SAFETY DATA SHEET Nitrogen (Expellant) REGULATORY INFORMATION US REGULATIONS (Federal, State) and INTERNATIONAL CHEMICAL REGISTRATION LAWS TSCA Listing This product contains ingredients that are listed on or exempt from listing on the EPA Toxic Substance Control Act Chemical Substance Inventory. EINECS Listing All ingredients in this product are listed on the European Inventory of Existing Commercial Chemical Substances (EINECS) or the European List of New Chemical Substances (ELINCS) or are exempt from...
  • Page 160 Kidde Fire Systems assumes no responsibility for personal injury or property damage resulting from use, handling or from contact with this product.
  • Page 161 IDENTIFICATION OF THE SUBSTANCE/PREPARATIONS AND OF THE COMPANY UNDERTAKING Product Name Carbon Dioxide (Fire Extinguishing Agent and Expellant) Other Trade Names Product Description Fire Extinguishing Agent and Expellant Manufacturer/Supplier Kidde Fire Systems 400 Main Street Address Ashland, MA 01721 (508) 881-2000 Phone Number Chemtrec Number...
  • Page 162 MATERIAL SAFETY DATA SHEET Carbon Dioxide (Fire Extinguishing Agent and Expellant) FIRST AID MEASURES Eyes Immediately flood the eye with plenty of warm water for at least 15 minutes, holding the eye open. Obtain medical attention if soreness or redness persists. Skin Gently warm affected areas.
  • Page 163 MATERIAL SAFETY DATA SHEET Carbon Dioxide (Fire Extinguishing Agent and Expellant) EXPOSURE CONTROLS/PERSONAL PROTECTION Respiratory Protection Not normally required under conditions of use as a portable fire extinguisher. For other applications creating oxygen deficient atmospheres, use a self contained breathing apparatus, as an air purifying respirator will not provide protection.
  • Page 164 MATERIAL SAFETY DATA SHEET Carbon Dioxide (Fire Extinguishing Agent and Expellant) TOXICOLOGICAL INFORMATION Chronic Toxicity/Carcinogenicity This product is not expected to cause long term adverse health effects. Genotoxicity This product is not expected to cause any mutagenic effects. Reproductive/Developmental Toxicity This product is not expected to cause adverse reproductive effects.
  • Page 165 MATERIAL SAFETY DATA SHEET Carbon Dioxide (Fire Extinguishing Agent and Expellant) REGULATORY INFORMATION US REGULATIONS (Federal, State) and INTERNATIONAL CHEMICAL REGISTRATION LAWS TSCA Listing This product contains ingredients that are listed on or exempt from listing on the EPA Toxic Substance Control Act Chemical Substance Inventory.
  • Page 166 MATERIAL SAFETY DATA SHEET Carbon Dioxide (Fire Extinguishing Agent and Expellant) OTHER INFORMATION HMIS Ratings HMIS Code for Health - 1 HMIS Code for Flammability - 0 HMIS Code for Reactivity - 0 HMIS Code for Personal Protection - See Section 8 Abbreviations N/A: Denotes no applicable information found or available CAS#: Chemical Abstracts Service Number...
  • Page 167 THIS PAGE INTENTIONALLY LEFT BLANK. October 2014 P/N 06-236115-001...
  • Page 169 Kidde is a registered trademark of Kidde-Fenwal, Inc. All other trademarks are property of their respective owners. These instructions do not purport to cover all the details or variations in the equipment described, nor do they provide for every possible contingency to be met in connection with installation, operation and maintenance.
  • Page 170 06-236115-003 July 2016 Supplement to Kidde Fire Systems® ECS Fire Suppression System with HFC-227ea Agent: Design, Installation, Operation, and Maintenance Manual Rev BA, P/N 06-236115-001 Placement Supervision LISTED LISTED APPROVED UL Listing File UL Listing File FM Approvals No. EX 4674 No.
  • Page 172 TABLE OF CONTENTS General ....................1 Component Descriptions ................ 2 Control Head Monitor with Explosion Proof Assembly, P/N 85-100000-100 ................2 2.1.1 Standards for US Explosion Proof Approval ..........3 2.1.2 Standards for Canadian Explosion Proof Approval ........3 Spacer, P/N 85-100000-002 (Optional) ............ 3 Installation Details ................
  • Page 173 THIS PAGE INTENTIONALLY LEFT BLANK. July 2016 06-236115-003...
  • Page 174: General

    Head Monitor suitable for mounting between the electric control head and the corresponding discharge valves. This document provides instructions to install the Control Head Monitor. ® For other details, see the Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: DIOM Rev BA, P/N 06-236115-001. 06-236115-003...
  • Page 175: Component Descriptions

    COMPONENT DESCRIPTIONS Control Head Monitor with Explosion Proof Assembly, P/N 85-100000-100 The Control Head Monitor with explosion proof assembly provides supervision for control head placement in normal and explosive environments in one easy to install component. The following specifications apply to the Control Head Monitor: •...
  • Page 176: Standards For Canadian Explosion Proof Approval

    For US and Canada Explosion proof installations, seal all conduits within 18 inches from the end of the component. WARNING 2.1.1 Standards for US Explosion Proof Approval Number Issue Date FM 3600 2011 FM 3615 2006 FM 3616 2011 FM 3810 2005 ANSI/ISA 60079-0 2013...
  • Page 177: Installation Details

    INSTALLATION DETAILS • Electric Control Head • Electric/Cable Control Head • Electric to N2 108 cu. in. Pilot Driver Installation of Electric Control Heads (P/N WK-890181-000 and 82-486500-010) Follow all instructions contained in the main body of the DIOM up to this section. Before installing a control head on an agent cylinder valve, ensure the control head is in the SET position (that is, the actuating pin is in the fully retracted or SET position).
  • Page 178 Figure 3. Order of Installation for Electric Control Head, P/N WK-890181-000 0.750 NPT TO FLEXIBLE CONDUIT ADAPTER FLEXIBLE CONDUIT OPTIONAL CONNECTION FOR MICROSWITCH (TERMINAL 2) PLUS OR HOT CONNECTION (TERMINAL 3) MINUS, NEUTRAL OR GROUND CONNECTION (TERMINAL 1) TERMINAL STRAP MICROSWITCH MICROSWITCH LEVER...
  • Page 179 The stackable control head (P/N 82-486500-010) cannot be used with the 3- inch valve cylinder (P/Ns 90-100600-100, 90-100601-100, 90-100900-001 and 90-100901-001), the 108 cubic inch Nitrogen Pilot Cylinder or any size of Nitrogen Driver. The stackable control head does not have sufficient force to activate these valves and may result in system failure.
  • Page 180: Installation Of Electric/Cable Operated Control Head

    Installation of Electric/Cable Operated Control Head, (P/N 81-895630-000 and WK-897494-000) Follow all instructions contained in the main body of the DIOM up to this section. The following procedures must be performed before attaching a control head to a cylinder valve. Before installing a control head on a nitrogen driver cylinder valve, ensure the control head is in the SET position (that is, the actuating pin is in the fully retracted or SET position).
  • Page 181: Installation Of Nitrogen Pilot Cylinder, P/N Wk-877940-000 And Mounting Bracket, P/N Wk-877845-000

    Installation of Nitrogen Pilot Cylinder, P/N WK-877940-000 and Mounting Bracket, P/N WK-877845-000 Follow all instructions contained in the main body of the DIOM up to this section. 1. Locate the nitrogen cylinder mounting bracket in an area where the cylinder valve assembly and control head will be protected from inclement weather by a suitable total or partial en- closure, preferably adjacent to the agent storage cylinders.
  • Page 182: Installation Of Stackable Pressure Operated Control Heads (P/N 82-878750-000)

    Installation of Stackable Pressure Operated Control Heads (P/N 82- 878750-000) Follow all instructions contained in the main body of the DIOM up to this section. Note: The Spacer (P/N: 85-100000-002) is only needed when installing an electric control head (P/N WK-890181-000, 81-895630-000, and 81-895630-000) onto a stackable pressure operated control head.
  • Page 183 5. Install the electric control head to the top port of the stackable pressure operated control head and tighten securely. Ensure that the pilot line is not pressurized and the actuating pins are in the SET position (that is, the actuating pins are in the fully retracted or SET position). Failure to follow this procedure will result in accidental discharge and possible WARNING death, personal injury, and property damage when the control head is installed...
  • Page 184: Preventive Maintenance

    PREVENTIVE MAINTENANCE Perform preventive maintenance per Table 1-1. Table 1-1. Preventive Maintenance Schedule Schedule Requirement Paragraph Semi-Annually Test electric control heads Semi-Annual Electric Control Head Test Electric control heads (including electric/cable operated combination control heads) must be tested semi-annually for proper operation. In addition, the Control Head Monitor must be tested to ensure it is functional.
  • Page 185: Parts List

    PARTS LIST Part Number Description Control Head Monitor, with Explosion Proof Assembly 85-100000-100 Control Head Monitor, with Explosion Proof Assembly 85-100000-002 Spacer, required when installing Control Head Monitor onto Stackable Pressure Operated Control Head July 2016 06-236115-003...
  • Page 187 All trademarks are properties of their respective owners. 400 Main Street Ashland, MA 01721 These instructions do not purport to cover all the details or variations in the equipment Ph:(508)881-2000 described, nor do they provide for every possible contingency to be met in connection with Fax:(508)881-8920 installation, operation and maintenance.
  • Page 188 06-237553-001 August 2016 ® Kidde Fire Systems 2” Valve and Safety Burst Disc Rebuild Kit and Instructions Addendum LISTED LISTED APPROVED UL Listing File UL Listing File FM Approvals No. EX 4674 No. EX 4674 Project ID 3054754 Jurisdiction: EAR...
  • Page 190 TABLE OF CONTENTS General ....................1 Component Descriptions ................ 2 2” Valve and Safety Burst Disc Rebuild Kit, P/N 85-150100-000 ................2 Post-Fire Maintenance ................3 2” Valve Disassembly ................3 2” Valve Assembly ................4 Safety Burst Disc Replacement ............... 5 Parts List .....................
  • Page 191 THIS PAGE INTENTIONALLY LEFT BLANK. August 2016 06-237553-001...
  • Page 192: General

    Kidde Engineered Fire Suppression System Designed for use with 3M™ 06-236553-001 Novec™ 1230 Fire Protection Fluid Design, Installation, Operation, and Maintenance Manual Kidde Fire Systems® ECS Advanced Delivery Fire Suppression System with 06-237256-001 3M™ Novec™ 1230 Fire Protection Fluid Design, Installation, Operation, and Maintenance Manual Kidde Fire Systems®...
  • Page 193: Component Descriptions

    COMPONENT DESCRIPTIONS 2” Valve and Safety Burst Disc Rebuild Kit, P/N 85-150100-000 The 2” Valve and Safety Burst Disc Rebuild Kit should be used to rebuild all 2” Valves after a discharge, including replacing the safety burst disc. Table 2. 2” Valve and Cylinder Rebuild Kit Contents Description Part Number 2"...
  • Page 194: Post-Fire Maintenance

    POST-FIRE MAINTENANCE Some components in the agent valve assembly will need to be inspected and serviced before recharging the cylinder/valve assembly. All O-rings must be replaced whenever a valve is disassembled. Part numbers for items which may require replacement are listed in Table 3. 2”...
  • Page 195: 2" Valve Assembly

    Table 3. Valve Components Figure Item No. Description 2” Valves Part Number O-ring, cap Included in Rebuild Kit O-ring, neck Included in Rebuild Kit Piston Assembly Included in Rebuild Kit Schrader core WK-220278-000 Table 4. Other Valve Components Other Materials Description Lubricant Parker Seal Co.
  • Page 196: Safety Burst Disc Replacement

    Safety Burst Disc Replacement Whenever the valve is rebuilt, the Safety Disc Assembly must be replaced. Refer to Figure 2 or Figure 3. CAUTION Before removing the valve, make sure that all pressure has been relieved from the cylinder. To relieve any remaining pressure, restrain the cylinder and WARNING depress the pressure check in the Supervisory Pressure Switch.
  • Page 197: Parts List

    VALVE SAFETY DISC WASHER SAFETY DISC SAFETY DISC RETAINER Figure 3. Installation of Safety Burst Disc on Valve (Valves Manufactured before May 2014) Table 5. Safety Disc Replacement Information Valve Size Torque Valve psig @ 70°F 2 in 38 ft lb 800-975 PARTS LIST Part Number...
  • Page 199 All other trademarks are properties of their respective owners. 400 Main Street Ashland, MA 01721 These instructions do not purport to cover all the details or variations in the equipment Ph:(508)881-2000 described, nor do they provide for every possible contingency to be met in connection with Fax:(508)881-8920 installation, operation and maintenance.
  • Page 200 06-236115-004 May 2016 Supplement to Kidde Fire Systems® ECS Fire Suppression System with HFC-227ea Agent: Design, Installation, Operation, and Maintenance Manual Rev BA, P/N 06-236115-001 Stainless Steel Nozzles LISTED LISTED APPROVED UL Listing File UL Listing File FM Approvals No. EX 4674 No.
  • Page 202 TABLE OF CONTENTS General ....................1-1 Component Descriptions ................ 1-2 Stainless Steel Discharge Nozzles............1-2 Stainless Steel Discharge Nozzle Parts List ..........1-4 360 Degree Nozzles ................1-4 180 Degree Nozzles: ................1-6 06-236115-004 May 2016...
  • Page 203 THIS PAGE INTENTIONALLY LEFT BLANK. May 2016 06-236115-004...
  • Page 204: General

    Stainless Steel are more beneficial. This document provides a component description and parts list for the new nozzles. ® For other details, see the Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: DIOM Rev BA, P/N 06-236115-001. 06-236115-004...
  • Page 205: Component Descriptions

    Note: Installation details and coverage areas for the Stainless Steel Nozzle are the same as ® the Brass Nozzles. Please refer to the Kidde Fire Systems ECS Fire Suppression Sys- tem with HFC-227ea Agent: DIOM Rev BA, P/N 06-236115-001 for further details.
  • Page 206 60° 30° Figure 3. 180° Discharge Nozzle Table 1. Dimensions–180° Discharge Nozzle Pipe Size ½ in (12.70 mm) 1.25 in (31.75 mm) 1.187 in (30.15 mm) 1.625 in (41.28 mm) 1.937 in (49.20 mm) ¾ in (19.05 mm) 1.5 in (38.10 mm) 1.375 in (34.92 mm) 1.95 in (49.53 mm) 2.296 in (58.32 mm)
  • Page 207: Stainless Steel Discharge Nozzle Parts List

    STAINLESS STEEL DISCHARGE NOZZLE PARTS LIST Only listed Kidde ECS System agent nozzles are to be used on Kidde ECS Systems. Failure to comply with this WARNING can result in unpredictable WARNING agent distribution. 360 Degree Nozzles 360 Degree Nozzle Part Number...
  • Page 208 360 Degree Nozzle Part Number Area (in 1/2 in NPT 3/4 in NPT 1 in NPT 1-1/4 in NPT 1-1/2 in NPT 2 in NPT 0.3927 90-194525-250 90-194526-246 0.4150 90-194525-257 90-194526-250 0.4280 90-194525-261 90-194526-257 0.4433 90-194525-266 90-194526-261 0.4649 90-194525-272 90-194526-266 0.4821 90-194525-277 90-194526-272...
  • Page 209: 180 Degree Nozzles

    180 Degree Nozzles: 180 Degree Nozzle Part Number Area (in 1/2 in NPT 3/4 in NPT 1 in NPT 1-1/4 in NPT 1-1/2 in NPT 2 in NPT 0.0770 90-194513-109 0.0810 90-194513-111 0.0820 90-194513-113 0.0875 90-194513-116 0.0931 90-194513-120 0.1030 90-194513-125 0.1072 90-194513-129 0.1190...
  • Page 210 180 Degree Nozzle Part Number Area (in 1/2 in NPT 3/4 in NPT 1 in NPT 1-1/4 in NPT 1-1/2 in NPT 2 in NPT 0.4056 90-194515-250 90-194516-250 0.4233 90-194515-257 90-194516-257 0.4400 90-194515-261 90-194516-261 0.4485 90-194515-266 90-194516-266 0.4734 90-194515-272 90-194516-272 0.4954 90-194515-277 90-194516-277...
  • Page 211 THIS PAGE INTENTIONALLY LEFT BLANK. May 2016 06-236115-004...
  • Page 213 All trademarks are properties of their respective owners. 400 Main Street Ashland, MA 01721 These instructions do not purport to cover all the details or variations in the equipment Ph:(508)881-2000 described, nor do they provide for every possible contingency to be met in connection with Fax:(508)881-8920 installation, operation and maintenance.

Table of Contents