18.3.7
The "Device check" submenu
Diagnostics ® Device check ® Start device check
Start of a device check.
• No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.
No
Diagnostics ® Device check ® Result device check
Indicates the result of the device check.
• Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the signal
amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check the
mounting position of the device and the dielectric constant of the medium.
• Check not done
Diagnostics ® Device check ® Last check time
Displays the operating time at which the last device check has been performed.
Display format
Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s