The "Device Check" Submenu - Endress+Hauser Levelflex FMP53 Operating Instructions Manual

Guided level-radar
Hide thumbs Also See for Levelflex FMP53:
Table of Contents

Advertisement

Levelflex FMP53
Start device check
Navigation
Description
Selection
Factory setting
Result device check
Navigation
Description
Display
Last check time
Navigation
Description
Additional information
Level signal
Endress+Hauser
18.3.7

The "Device check" submenu

Diagnostics ® Device check ® Start device check
Start of a device check.
• No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.
No
Diagnostics ® Device check ® Result device check
Indicates the result of the device check.
• Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the signal
amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check the
mounting position of the device and the dielectric constant of the medium.
• Check not done
Diagnostics ® Device check ® Last check time
Displays the operating time at which the last device check has been performed.
Display format
Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s
Description of device parameters (operating menu)
151

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Levelflex FMP53 and is the answer not in the manual?

Questions and answers

Table of Contents