The "Device Check" Submenu - Endress+Hauser Levelflex FMP50 Operating Instructions Manual

Guided level-radar level measurement in liquids
Hide thumbs Also See for Levelflex FMP50:
Table of Contents

Advertisement

Description of device parameters (operating menu)
Start device check
Navigation
Description
Selection
Factory setting
Result device check
Navigation
Description
Display
Last check time
Navigation
Description
Additional information
Level signal
168
19.3.7

The "Device check" submenu

Diagnostics ® Device check ® Start device check
Start of a device check.
• No
No device check is performed.
• Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.
No
Diagnostics ® Device check ® Result device check
Indicates the result of the device check.
• Installation ok
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the signal
amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check the
mounting position of the device and the dielectric constant of the medium.
• Check not done
Diagnostics ® Device check ® Last check time
Displays the operating time at which the last device check has been performed.
Display format
Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s
Levelflex FMP50