RECOMMENDED INSTALLATION TEMPLATE
Module "600"
Max. dimensions of installation bracket
Max. dimensions of installation bracket
INSTALLING THE "MODULE 600" UNIT
- Choose the place for unit installation according
to the layout of the room, the number of units
to be installed, and any limitations imposed
by the architecture. Check the chosen place is
suitable for installation and maintenance work
on the unit.
- Install four M8 threaded rods into the ceiling to
hold the frame.
To install the FCLI unit, proceed as follows:
- upturn the box of the FCLI cassette-type fan
coil
- open the cardboard box
- remove the box; you are advised to make cuts
on the corners of the box and remove the
cardboard in separate pieces
- remove the upper part of the packaging frame
(that protects the unit during transportation)
- remove the fan grille and take out the Inverter
The FCLI 600x600 driver inverter is integrated to
the group motor-fan.
- If it is necessary to fit any accessories (fresh
air kit or delivery to an adjacent room, hot
water valve), carry out these operations before
installing the machine on the ceiling.
WARNING: consult the relevant manuals of
the accessories
Do not handle the unit using the water
connections; use the specific brackets for this
purpose.
- lift the unit carefully by means of the brackets
and, keeping it slightly inclined, attach it to
the 4 threaded bars using 8 nuts (4 of which
24
Max. dimensions of water connections
are self-locking). Use the nuts to adjust the
height of the unit; finally, check that the unit is
installed in a horizontal position
- feed the hydraulic pipes through the
suspended ceiling to the attachment plate on
the unit
- make the plumbing connections as described in
the relative chapter
- Take the condensate discharge piping to the
relative fitting on the attachment plate
- bleed the system (the drain valve for the 2-pipe
circuit is on the outside of the attachment
plate). The drain valve for the heat circuit of
4-pipe systems is inside (to access it, remove
the polystyrene tray)
- make the condensate drainage connection as
described in the relative chapter
- the electric box is supplied with the grille
accessory (GLLI/GLF10)
- bring the power supply and command cables
close to the electric box; ensure the cables are
long enough to follow the movement of the
electric box on the guides during the assembly
and disassembly phases
- connect the Inverter to the electric box, using
the cables supplied
- consult the manuals of the grille accessories;
the instructions for assembling and connecting
the electric box can be found in the manual
supplied with the grille accessory
- After completing the connections and inserting
the electric box in its seat in the FCLI unit, fix it
Module "840"
Max. dimensions of
water connections
Max. dimensions of
installation bracket
Max. dimensions of
installation bracket
with the two screws.
WARNING: fix the safety cable to the fixing
screw of the electric box (to the side of the
water connections). The snap-hook of the
safety cable must then be connected to the
grille frame.
- The grille frame must be positioned so that the
glass with the AERMEC logo is in line with the
corner of the electric box.
- Fix the grille to the safety cable.
- Fix the grille with the 4 screws.
WARNING!! Tighten the screws with a
maximum tightening torque of 0.45 Nm. You
are advised to use a screwdriver. Do not use
non-calibrated electric screwdrivers. The tray
will be irreparably damaged if tightened too far.
- Remove the suction grille by means of the two
¼ turn bolts.
- Assemble the air filter.
- Reassemble the suction grille by means of the
two ¼ turn bolts.
- adjust the position of the unit from the support
bracket by means of the nuts so that the unit
is level and the frame rests slightly on the
suspended ceiling
- Start the fan coil unit and carry out a function
test, the functions are described in the user
manual.
• Installing near a wall
If the unit is to be installed near a wall, the
corresponding delivery outlet can be closed
using the gasket supplied.
Condensate drain
side
Max. dimensions of
installation bracket
Max. dimensions of
installation bracket