9 SENSOR SELECT

When reselect sensors, the sensor curve will be transferred into the standard value. For example, if
temperature sensor is SGH (120°C resistor type), its sensor curve is SGH (120°C resistor type); if
select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
When there is difference between standard sensor curves and using sensor, user can chose
"Defined sensor", and input defined sensor curve.
When input the sensor curve, X value (resistor) must be input from small to large, otherwise, mistake
occurs.
If select sensor type as "None", temperature, pressure and fuel level which LCD displays will be "---".
If there is no pressure sensor only pressure low alarm switch, user must set the sensor as "None",
otherwise, maybe pressure low alarm shutdown occurs.
The headmost or backmost values in the vertical coordinates can be set as same as below,