ACCON-NetLink-PRO
compact not
reachable
The program
®
STARTER
has
problems when
accessing a
MICROMASTER
®
SINAMICS
ACCON-NetLink-PRO compact
NetLink-PRO
compact are not
identical
Ports have to be
released in the
firewall
Failure and
application
monitoring too low
®
or
NetLink-PRO
compact have to be
in the same network
segment
To search the
ACCON-NetLink-PRO
compact the UDP
ports 25342 and
25343 have to be
released. For the
communication the
TCP port 7777 and
102 (RFC1006) have
to be released.
1. Increase the
timeout in the
PG/PC-Interface to
80000ms.
2. Increase failure
monitoring to 200ms
and application
monitoring to
5000ms
46
Need help?
Do you have a question about the ACCON-NetLink-PRO and is the answer not in the manual?