TROUBLE SHOOTING
Error
Power LED does not
light
Active LED is blinking
red
Connect LED is
blinking red
Link LED does not light
green
Configuration of the ACCON-NetLink-PRO compact via ACCON-S7-
NET
The message
»ACCON-NetLink-PRO
compact cannot be
parametrized now.«
appears
The message »Wrong
password« appears
Setting TCP/IP parameters
No ACCON-NetLink-
PRO compact is
reachable via the
entered IP address
ACCON-NetLink-PRO compact
Cause
-ACCON-NetLink-
PRO compact has
no voltage supply
-The used MPI
bushing has not the
necessary 24 VDC
ACCON-NetLink-
PRO compact
exception error on
Ethernet side
ACCON-NetLink-
PRO compact
exception error on
MPI/PROFIBUS side
No connection to
the Ethernet
ACCON-NetLink-
PRO compact is
active on the bus
during
parametrization
Password incorrect
and/or
parametrization
time exceeded
-ACCON-NetLink-
PRO compact is not
online or still
starting
-IP configuration of
PC and ACCON-
Solution
- Plug
MPI/PROFIBUS cable
on PLC interface
- Apply 24 VDC
externally
Plug MPI/PROFIBUS
cable again on the
PLC interface
Plug MPI/PROFIBUS
cable again on the
PLC interface
Check Ethernet
connection
ACCON-NetLink-PRO
compact has to be
inactive during
parametrization
Enter correct
password and mind
parametrization
time (see side 37)
-Activate ACCON-
NetLink-PRO
compact or
complete starting
procedure
-PC and ACCON-
45