Installation considerations

The Rosemount
Mounting at the tank foot may be convenient when you would like to have easy access to
measuring data, diagnostics and other information on the optional integral display.
The Rosemount 2410 Tank Hub can also be mounted on the tank roof if this is the
preferred location. In case the tank hub is exposed to long periods of sunshine, a sunshade
should be used to prevent it from being heated to temperatures above the maximum
operating temperature.
Ensure that environmental conditions are within specified limits as listed in
and reference
Ensure that the Rosemount 2410 is installed such that it is not exposed to higher pressure
and temperature than specified in
The multi-tank version of the Rosemount 2410 Tank Hub is able to serve several tanks. In
that case it may be placed at a suitable location further away from the tanks.
The Rosemount 2410 is designed with two Tankbus terminals and several cable entries
which allows alternative cable routings to suit various requirements.
Do not install the Rosemount 2410 in non-intended applications, for example
environments where it may be exposed to extremely intense magnetic fields or extreme
weather conditions.
Important
Check the Rosemount 2410 Tank Hub for any signs of damage prior to installation. Ensure
that the glass on the integral display is undamaged, and O-rings and gaskets are in good
condition.
3.2.1
Installation planning
It's a good idea to plan the installation in order ensure that all components in the system
are properly specified. The planning stage should include the following tasks:
Make a plan of the site and specify suitable locations for the devices
Consider power budget
Specify cabling and connections (for example whether devices will be "daisy-chained"
or not)
Specify cable glands that will be needed for the various devices
Specify location of terminators on the Tankbus
Make a note of identification codes such as Unit ID/Device ID of each device
Assign Modbus
tank database of the Rosemount 2410 and the tank database of the Rosemount 2460
System Hub (see the Rosemount Tank Gauging
document no. 00809-0300-5100 for more information)
See
Electrical installation
26
2410 Tank Hub may be installed on various locations at the plant.
data.
Specifications and reference
®
addresses for level gauges and other tank devices to be used in the
for more information on cables and glands.