Table 6-3: Troubleshooting chart
Symptom
No communication with
one or more devices on
the Tankbus
Rosemount 2410 Tank Hub
(continued)
Possible cause
Wiring
Service and troubleshooting
Action
Check that the devices appear in the Device Live
List (see
View the device live list in
TankMaster
).
Check diagnostics information, see
configure diagnostic registers using
TankMaster
for warning or error messages.
Check that wires are properly connected to the
terminals.
Check for dirty or defective terminals.
Check wire insulation for possible short circuits
to ground.
Check diagnostics information (see
configure diagnostic registers using
TankMaster
) for information that indicate bad
communication on the Tankbus: - Input
registers 1300 to 1328 provide general
information on Tankbus communication - Input
registers 1330 to 1648 provide information on
specific devices on the Tankbus.
Check diagnostics information (see
configure diagnostic registers using
TankMaster
) for possible hardware faults that
indicate short circuits or ground faults: - check
Input Register 1326 for short circuits - check
Input Register 1328 for ground faults.
Check that there are no multiple shield
grounding points
Check that the cable shield is grounded at the
power supply end (Rosemount 2410 Tank Hub)
only.
Check that the cable shield is continuous
throughout the Tankbus network.
Check that the shield inside the instrument
housing does not come into contact with the
housing.
Check that there is no water in conduits.
Check for proper polarity at the terminals
(Rosemount 5300 and 5408).
Use shielded twisted pair wiring.
Connect wiring with drip loops.
Check the loop impedance.
December 2019