6.2.13
Loading the default database using TankMaster
The various configuration parameters of the Rosemount 2410 Tank Hub is stored in a
Holding Register database. The Holding Register factory setting is stored in the default
database. TankMaster WinSetup offers the option to load the default database. This may
be useful if, for example, you would like to try out new database settings and then be able
to reload the original factory settings.
Prerequisites
In case error messages appear or other problems occur concerning the database,
troubleshooting the cause of these problems is recommended before loading the default
database.
It is recommended that the current database is backed up before the Default Database is
loaded. See
to save the current database.
Note
When the default database is loaded to the Rosemount 2410 Tank Hub, measurement
units are reset to Metric units.
Note
The device address remains unaltered when the default database is loaded.
Procedure
1. In the TankMaster WinSetup workspace window, select the desired device icon.
2. Right-click and select View Holding Register.
3. Choose the All option and type 65510 in the Start Register input field.
4. Type the desired number of registers to be displayed in the Number of Registers
5. In the Value input, type 65510 .
6. Click the Apply button to load the default database.
Rosemount 2410 Tank Hub
Backing up a device configuration using TankMaster
field and click the Read button.
Service and troubleshooting
December 2019
for information on how
95