Service and troubleshooting
December 2019
6.2.12
Relay output configuration
To change the Normally Open/Normally Closed settings of the K1 and K2 relays, do the
following:
Procedure
1.
2.
3. Remove the front cover.
4. Remove the plastic display cover.
5. Switch the jumpers to the desired settings: Normally Open (NO) or
6. Replace the plastic display cover and the front cover.
94
Disconnect the power supply.
Disconnect the relays.
A. Front cover
Normally Closed (NC).
A
B
A. Relay K1: NO / NC
B. Relay K2: NC / NO
Note
Ensure that o-rings and seats are in good condition prior to mounting the cover in
order to maintain the specified level of ingress protection.
A
Reference Manual
00809-0100-2410