Operation Data Acquisition Mode - Mitsubishi Electric AE-200A Instruction Book

Air conditioning control system centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

4-2. Operation Data Acquisition Mode

This screen allows the user to activate or deactivate the Operation Data Acquisition function, and to select
between the two data acquisition modes with different minimum interval settings for the AE-200/AE-50/EW-50 to
collect operation data from the connected units.
Click [Maintenance] in the menu bar, and then click [Operation Data Acquisition Mode] to access the Operation
Mode Acquisition Mode screen.
The default setting for this function is set to deactivate (OFF), and all the unit addresses on the screen appear
with a black background.
Note: This function enables the user to collect data for outdoor units, indoor units, BC controllers, and Air To Water (PWFY)
units.
Note: The [Short Interval] mode is for use by Mitsubishi Electric Corporation to conduct research. Overseas sales office
users should select [Normal] mode.
Acquisition Mode
Select OFF, Normal, or Short
Interval.
Address selection field
Select All
Deselect All
Refresh
Click to import the settings
from AE-200/AE-50/EW-50.
Item
OFF
Normal
Acquisition
Mode
Short
Interval
Re-search
Address selection field
Deselect All
Select All
WT07324X02
Use this mode to deactivate the Operation Data Acquisition function.
Use this mode to acquire the operation data of the units selected in the Address selection
field at a minimum data acquisition interval of 2 minutes.
Note: If 40 or more indoor units are connected, data acquisition interval may be stretched by
multiples of two minutes.
Use this mode to acquire the operation data of the units selected in the Address selection
field at a minimum data acquisition interval of 1 minute.
Note: If 10 or more indoor units are selected, data acquisition interval may be stretched by
1-minute increments. Deselecting some units will decrease the data acquisition interval.
Note: The [Short Interval] mode is for use by Mitsubishi Electric Corporation to conduct research.
Overseas sales office users should select [Normal] mode.
Click to update all information in the address selection field with the most recent information.
Select the addresses of the units to acquire the operation data.
The backgrounds for the selected units will appear in green, and for the deselected
units will appear in gray. The backgrounds for the units that are not connected to
AE-200/AE-50/EW-50, and for the units that do not support this function will appear in black.
Click an address to select it, and click again to deselect.
Click to deselect 50 units on one of the two tables at once.
Note: Units 1-50 are on one table, and 51-100 are on the other table.
Click to select 50 units on one of the two tables at once.
Note: Units 1-50 are on one table, and 51-100 are on the other table.
Description
12
Re-search
Deselect All
Select All
Save Settings
Click to send the settings to
AE-200/AE-50/EW-50.