4. Maintenance

4-1. Operation Data Display

This screen displays the operation data that is acquired from the connected units by the AE-200/AE-50/EW-50
at regular intervals. Click [Maintenance] in the menu bar, and then click [Operation Data Display] to access the
Operation Data Display screen.
Note: To display the operation data on this screen, the settings for "Operation Data Acquisition Mode" need to be set.
Make the settings according to the instructions detailed in section 4-2.
Note: The operation data displayed on this screen will vary, depending on the unit model.
Refer to the Service Handbook that came with the unit.
Address
Start date/time
End time
Export as CSV
Click to export operation
data in the CSV file format.
Item
Address
Start date/time
End time
Update
Display start time data
Display operation data
Data display field
Export as CSV
WT07324X02
Select the address of the unit to display its operation data.
Enter the start date/time for the time period for which operation data will be displayed.
Enter the end time for the time period for which operation data will be displayed.
Note: Up to 24 hours worth of data can be displayed at once.
If the start time is after the end time, the start time and end time will be regarded as the
other way around, and the operation data between the end time and the start time for the
specified date will be displayed.
Click to display the latest operation data of the selected unit.
Click to display the operation data of the selected unit at the specified start time.
Note: If the Operation Data Acquisition Mode is set to [Normal], data for odd minutes will not be
displayed. (See section 4-2.)
Click to display the operation data of the selected unit in a specified time range.
Note: Regardless of the Operation Data Acquisition Mode setting, operation data will be
displayed at 2-minute intervals. (See section 4-2.)
Note: If 40 or more indoor units are connected, data acquisition interval may be stretched by
multiples of two minutes.
Operation data of the selected unit will be displayed in this field.
Click to export the operation data that are displayed in the Data display field in the CSV
file format. Only the operation data that are displayed when [Display operation data] is
clicked can be exported. (An empty CSV file will be output for the operation data that are
displayed when [Update] or [Display start time data] is clicked.)
Description
10
Update
Click to display the latest
operation data of the
selected unit.
Display start time data
Display operation data
Data display field