3. Logging in to the Web Browser for Remote
Monitoring User
(1) Enter the web page address in the address field of the Web browser as follows:
http:// [IP address of each AE-200/AE-50/EW-50]/en/maintenance.html
Press the [Enter] key. A login screen will appear.
Note: If the IP address of the
the web page address is [http://192.168.1.1/en/maintenance.
html].
Note: Default IP address of AE-200/AE-50/EW-50 is [192.168.1.1].
When one or more AE-50/EW-50 controllers are
connected, none of their IP addresses should overlap. The
recommended IP address ranges are as follows.
AE-200: Between [192.168.1.1] and [192.168.1.40]
AE-50/EW-50: Between [192.168.1.211] and [192.168.1.249]
Note: Log in to the AE-200/AE-50/EW-50 Web browser
respectively to monitor the units that are under the control of
AE-200/AE-50/EW-50. The Web browser cannot be switched
between the AE-200/AE-50/EW-50.
Note: If the login screen does not appear then take the steps below
to delete the temporary files.
<Internet Explorer>
1. Click [Tools] in the menu bar, then click [Internet options].
2. On the [General] tab, click [Delete] in the middle of the
window.
3. In the [Delete Browsing History] window, click [Delete].
<Java>
1. Click [Control Panel] from the Start menu.
2. Click the [Java] icon to launch the Java Control Panel.
3. On the [General] tab, click [Settings] in the [Temporary
Internet Files] section.
4. Click [Delete Files].
5. In the [Delete Files and Applications] window, click [OK].
Note: This web page can only be displayed in English.
Note: You can add the web page address to your Favorites for easy access in the future.
(2) Enter the user name and the password in the login screen, and click [Login]. A setting screen will appear.
The table below shows the default user name, password, and functions that are available for remote
monitoring users.
User
Remote
monitoring
user
Note: It is recommended to change the default user name and password so that the users other than the remote monitoring users will
not be able to change the settings.
*1 If the Serial No. is "15A13-701," the default password is "rm15A13701."
WT07324X02
AE-200/AE-50/EW-50
Default
Default password
user name
remotemonitor
rm + Serial No.
is [192.168.1.1],
Maintenance
*1
Malfunction Log
User Settings
8
Available functions
Operation Data Display
Operation Data Acquisition Mode
Unit Error
User Settings