Interpret The Status Indicators - Allen-Bradley Rockwell Automation 1734-AENT User Manua

Point i/o ethernet/ip adapter module
Hide thumbs Also See for Rockwell Automation 1734-AENT:
Table of Contents

Advertisement

Interpret the
Status Indicators
1
LED Status Indicators
ATTENTION
You must use Series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O
modules will not work with this adapter.
Module
Status
0
0 2
Network
Activity
Network
Status
PointBus
Status
1734-AENT
System
Power
Field
Power
Indication
Probable Cause
System Power
Off
Not active; field power is off or dc-dc converter problem
Green
System power on; dc-dc converter active (5V dc)
Field Power
Off
Not active; field power is off
Green
Power on; 24V dc present
Indication
Probable Cause
Module Status
Off
No power applied to device
Flashing Red/Green
LED powerup test (module self-test)
Green
Device is operating normally
Flashing Red
Recoverable fault has occurred: Firmware (NVS) update
Module Status
Network Activity
Network Status
PointBus Status
System Power
Field Power
Publication 1734-UM011A-EN-P - February 2004