C-10
1734-POINT I/O Module/RSLogix 5000 Controller Tag Reference

Analog 2 Channel Input

Publication 1734-UM011A-EN-P - February 2004
1734-IE2C
2 Channel Analog Current Input
Configuration Data
Low Engineering Channel 0
High Engineering Channel 0
Digital Filter Channel 0
Low Alarm Limit Channel 0
High Alarm Limit Channel 0
Low Low Alarm Limit Channel 0
High High Alarm Limit Channel 0
Range Type Channel 0
Limit Alarm Latch Channel 0
Alarm Disable Channel 0
Low Engineering Channel 1
High Engineering Channel 1
Digital Filter Channel 1
Low Alarm Limit Channel 1
High Alarm Limit Channel 1
Low Low Alarm Limit Channel 1
High High Alarm Limit Channel 1
Range Type Channel 1
Limit Alarm Latch Channel 1
Alarm Disable Channel 1
Notch Filter (Channel 0 & 1)
Real Time Sample (Channel 0 & 1)
Data Type Default
Valid Data Values
Value
INT
3,277
-32,768 to 32,767
INT
16,383
-32,768 to 32,767
INT
0
0 to 10,000 ms
INT
3,113
-32,768 to 32,767
INT
16,547
-32,768 to 32,767
INT
2,867
-32,768 to 32,767
INT
16,793
-32,768 to 32,767
SINT
3
3=4-20mA
8=0-20mA
SINT
0
0=No Latching
1=Alarms Latch
SINT
0
0=Alarms Enabled
1=Alarms Disabled
INT
3,277
-32,768 to 32,767
INT
16,383
-32,768 to 32,767
INT
0
0 to 10,000 ms
INT
3,113
-32,768 to 32,767
INT
16,547
-32,768 to 32,767
INT
2,867
-32,768 to 32,767
INT
16,793
-32,768 to 32,767
SINT
3
3=4-20mA
8=0-20mA
SINT
0
0=No Latching
1=Alarms Latch
SINT
0
0=Alarms Enabled
1=Alarms Disabled
SINT
2
1=50Hz
2=60Hz
4=250Hz
6=500Hz
INT
100
0 to 10,000 ms