Interpret Status Indicators - Allen-Bradley C Series Installation Instructions Manual

Point i/o 2 current and 2 voltage input analog modules
Table of Contents

Advertisement

18 POINT I/O 2 Current and 2 Voltage Input Analog Modules

Interpret Status Indicators

Refer to the following diagram and table for information on how to interpret the
status indicators.
1734-IE2C,
1734-IE2CK
Indicator Status for Modules
Status
Module status
Off
Green
Flashing green
Flashing red
Red
Flashing red/green Device is in self-test mode.
Publication 1734-IN027D-EN-E - December 2018
Module status
Network status
Status of input 0
Status of input 1
Description
No power applied to device.
Device operating normally.
Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Recoverable fault.
Unrecoverable fault occurred. Self-test failure present (checksum
failure, or ramtest failure at cycle power). Firmware fatal error
present.
1734-IE2V,
1734-IE2VK
Module
Module status
Status
Network
Network status
Status
NODE:
Analog
Voltage
Input
Status of input 0
0
Status of input 1
1