Scrn
Description
No.
139.
VESDA Device - This screen lists all devices of a particular Xtralis VESDA
product (e.g. Each VLP detector connected to VESDAnet will be displayed with
their respective unique detector number under the VLP/VLS screen). To access
the device through the LCD Programmer, highlight the device and press
Note: For details of menu descriptions refer from "Screen Number 6, on page 13"
to "Screen Number 137, on page 39."
140.
System/All Devices - This alternative permits setting up and managing the
parameters of the entire system connected to VESDAnet.
141.
Status - This screen presents the current status for all the devices connected to
VESDAnet. It displays the smoke level from the detector with the highest reading.
The current status of Alarms and Faults for each device is listed under their
respective device names.
142.
System Control - The four functions under System Control are the same as the
functions performed by the buttons on the Display Module.
Mode - This controls the mode of the LCD Numerical display on the Display.
Use the +, -, and the
-
Current Sector - Display the First Alarm Sector in VLS Display
-
Sensitivity - Displays the sensitivity level
-
Smoke Level - Displays the current smoke level
-
Address Number - Displays the assigned VESDA Zone number for the
detector
Silence - Silences beeping sound of the detector
Scan - Selecting this option in a VLS Display commences a Scan sequence of
the assigned VLS Detector
Reset - Resets faults
Isolate - Starts and stops isolation of the detector
143.
AutoLearn - The AutoLearn function allows setting the thresholds automatically.
The detector measures the ambient over the set period and will establish the
smoke and alarm thresholds accordingly. Enter the number of days, hours and
minutes over which the AutoLearn function is to apply.
Parameter
AutoLearn
144.
Set Date & Time - This screen permits setting the date, time and day.
145.
Weekend - Placing a
weekend. By default Saturday and Sunday are set as weekend days.
146.
Holidays - Insert the first and the last day of holidays to set different smoke
thresholds during this period.
147.
Users - This screen presents sub menus to display and manage user information:
Change User Details
Add User
Delete User
40
key to change the mode
Default
Minimum
14 days
0 days
0 hours
0 hours
0 minutes
15 minutes
against the relevant week day will denote it as being
Xtralis VESDA
Min.
Access
Level
USR
.
USR
USR
USR
ADM
Maximum
15 days
23 hours
59 minutes
USR
ADM
ADM
USR
www.xtralis.com
®