Xtralis VESDA LCD Programmer Product Guide
Scrn
Description
No.
10.
Select Events - This function assists in easier viewing of the logged events. The
events can be sorted as per the categories displayed. After selecting the events,
proceed to Screen 9 to view the events.
End Date - This allows viewing of events up to the date mentioned in the date
field. You can input the required date in the date field.
End Time - This is the time up to which events will be displayed for viewing. You
can input the required time in the time field.
Events to view -
-
Smoke Level - A
-
Alarms - A
-
Faults - A
-
User Action - To view a log of user actions place a
-
Clear Log - This function is only available with DST access.
To clear the log of events highlight Start and press
Use the + key to place a
11.
Zone Control - The four functions under Zone/Address control are the same as
the functions performed by the buttons on the display module.
Mode - This controls the mode of the Multi-Segment LCD display on any display
connected to that zone. Use the +, -, and the
-
Sensitivity - Displays the sensitivity level of Fire 1
-
Smoke - Displays the current smoke level
-
Address Number - Displays the assigned Address number for the detector
Silence - Silences the beeping sound of the detector
Reset - Resets fire and fault conditions
Isolate - Starts and stops isolation of the detector
12.
Smoke Thresholds - This screen lists screens 13 to 19 as options available for
setting smoke thresholds.
13.
Day Thresholds - This screen allows viewing and changing the current Fire 2, Fire
1, Action and Alert thresholds for day time.
Parameter
Fire 2/Full Scale
Fire 1/Fire
Action/Pre/
Alarm
Alert
14
against Smoke Level will display logged smoke levels
against Alarms displays a log of alarms
against Faults displays a log of the logged faults
and - key to insert a X and deselect the option.
Default
Minimum
2.000% obs/m
0.020% obs/m
(0.625% obs/ft)
(0.0062% obs/ft)
0.200% obs/m
0.015% obs/m
(0.0625% obs/ft)
(0.0046% obs/ft)
0.140% obs/m
0.010% obs/m
(0.044% obs/ft)
(0.0031 obs/ft)
0.080% obs/m
0.005% obs/m
(0.025% obs/ft)
(0.0015% obs/ft)
against user action
.
keys to change the mode
Maximum
20.000% obs/m
(6.25% obs/ft)
2.000% obs/m
(0.6250% obs/ft)
1.995% obs/m
(0.6234% obs/ft
1.990% obs/m
(0.6218% obs/ft)
Xtralis VESDA
®
Min.
Access
Level
ADM
USR
ADM
ADM
www.xtralis.com