Xtralis VESDA LCD Programmer Module Product Manual page 35

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
78.
Communications - The Communications screen allows settings for:
Net Delay - This function sets the maximum time for a message to travel
around the network and return to the originating device. If the message does
not return within the prescribed time, it is presumed lost and will be resent
Pref. Port - This allows you to assigning a preferred port for communication
Health Check - This function sets the frequency of health-check messages
sent around the system
Open-ended - In an open-ended VESDAnet loop select the port that is not con-
nected to the VESDAnet loop.
Parameter
Network delay
Preferred port
Health check
Open - ended
79.
Miscellaneous -
UL Version - A
ifications.
Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms
Latch Faults - This provides a YES/NO option to latch/unlatch all Faults
GP Input - The GP Input permits setting the general purpose input functions.
For details on GPI functions please refer to the VLS Product Guide.
80.
VLC Detector - Lists functions available for accessing and managing the
properties of the selected VLC detector. Select the required option and press
81.
Status - Displays the current Status of the Address
Smoke Level - Displays the current smoke level in the VESDA Zone measured
in obs%m or (ft)
Alarms - If the detector is in an alarm mode, the alarm stage is displayed
Faults - List of faults generated for each Xtralis VESDA device assigned to the
Address
Isolated - The Isolated status is reported only if the detector has been isolated
Current% Flow - Reports the current percentage of air flow
SW Version - Displays the software version in the detector
Cfg Code - This is a configuration code set during production
82.
Event Log -
View Events
Select Events
83.
View Events - Lists a log of events
www.xtralis.com
Default
15 seconds
A
45 seconds
none
against this indicates that the device is set to meet UL spec-
Parameter
UL Version
Latch Alarm
Latch Fault
Xtralis VESDA LCD Programmer Product Guide
Minimum
Maximum
10 seconds
45 seconds
N/A
N/A
40 seconds
60 seconds
N/A
N/A
Default
Enabled
Enabled
Enabled
Min.
Access
Level
DST
ADM
DST
USR
.
USR
USR
USR
29