Xtralis VESDA LCD Programmer Module Product Manual page 40

Table of Contents

Advertisement

Xtralis VESDA LCD Programmer Product Guide
Scrn
Description
No.
103.
Factory Defaults -
Factory Defaults - To restore factory defaults, highlight Restore and press
Defaults OK - Highlighting Start and pressing
Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
104.
Communications - The Communications screen allows settings for:
Net Delay - This function sets the maximum time for a message to travel around
the network and return to the originating device. If the message does not return
within the prescribed time, it is presumed lost and will be resent
Prof. Port - This allows you to assign a preferred port for communication
Health Check - This function sets the frequency of health-check messages sent
around the system
Open-ended - In an open-ended VESDAnet loop select the port that is not
connected to the VESDAnet loop.
Parameter
Network delay
Preferred port
Health check
Open - ended
105.
Miscellaneous -
UL Version - A
specifications.
Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms
Latch Faults - This provides a YES/NO option to latch/unlatch all Faults
GP Input - The GP Input permits setting the general purpose input functions.
For details on GPI functions please refer to the VLP Detector Guide.
106.
Ancillary Devices - Should be put under the same flow line as detectors. Select
the device by highlighting it and press
107.
Display/Relays - Should be put under the same flow line as detectors. Select the
Display/Relay and press
108.
Status - Displays the current status of the Display/Relay
Faults - List of faults generated for Display/Relay connected to VESDAnet
SW Version - Displays the software version of the Display/Relay
Cfg Code - This is a configuration code set during production
34
Default
Minimum
15 seconds
10 seconds
A
N/A
45 seconds
40 seconds
none
N/A
against this indicates that the device is set to meet UL
Parameter
Default
UL Version
Enabled
Latch Alarm
Enabled
Latch Fault
Enabled
.
.
will acknowledge Factory
Maximum
45 seconds
N/A
60 seconds
N/A
Xtralis VESDA
®
Min.
Access
Level
.
DST
ADM
DST
ADM
DST
USR
USR
USR
www.xtralis.com