Xtralis VESDA LCD Programmer Module Product Manual page 27

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
46.
Select Events - This function assists in easier viewing of the logged events. The
events can be sorted as per the categories displayed. After selecting the events,
proceed to Screen 45 to view the events.
End Date - This allows viewing of events up to the date mentioned in the date
field. You can input the required date in the date field.
End Time - This is the time up to which events will be displayed for viewing.
You can input the required time in the time field.
Events to view -
-
Smoke Level - A
-
Alarms - A
-
Faults - IA
-
User Action - To view a log of user actions place a
-
Clear Log - To clear the log of events highlight Start and press
Note: Use the + key to place a
47.
Address Control - The four functions under Address Control are the same as the
functions performed by the buttons on the Display Module.
Mode - This controls the mode of the LCD Numerical display on the Display.
Use the +, -, and the
-
Sensitivity - Displays the sensitivity level
-
Smoke - Displays the current smoke level
-
Address Number - Displays the assigned VESDA Zone number for the
detector
-
Current Sector - Displays the First Alarm Sector in a VLS Detector
Silence - Silences the beeping sound of the detector
Reset - Resets faults
Isolate - Starts and stops isolation of the detector
48.
Smoke Thresholds - This screen lists screens 49 to 58 as options available for
setting Smoke Thresholds.
49.
Day Thresholds - This screen allows viewing and changing the current Fire 2, Fire
1, Action and Alert thresholds for day time.
www.xtralis.com
against Smoke Level will display logged smoke levels
against Alarms displays a log of alarms
against Faults displays a log of the logged faults
-
and
key to insert a x to deselect the option.
Parameter
Select Events
end date
end time
Events to View
Smoke Level
Alarms
Faults
User Action
keys to change the mode
Xtralis VESDA LCD Programmer Product Guide
against User Action
Default
Selectable
Selectable
Enabled
Enabled
Enabled
Enabled
Min.
Access
Level
ADM
DST
.
USR
ADM
ADM