Xtralis VESDA LCD Programmer Module Product Manual page 29

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
55.
Delays & Thresholds - This screen displays the delays and thresholds for the
VLS.
-
Delays - The time before a VLS will commence scanning, once the lowest
threshold is reached.
-
Sector Time - The time spent looking at each sector after the initial fast
scan sequence. This allows air sample from a previous pipe to clear out
from the detector before it starts reading the air sample from the next pipe.
-
Thresholds - The smoke threshold for the VLS
-
Day Threshold - The day smoke threshold for the VLS
-
Night Threshold - The night smoke threshold for the VLS
Parameter
Delay
Sector Time
Threshold
Day Threshold
Night Threshold
www.xtralis.com
Xtralis VESDA LCD Programmer Product Guide
Default
Minimum
3 seconds
0 seconds
10 seconds
8 seconds
0.02% obs/m
(0.0062% obs/ft)
0.02% obs/m
(0.0062% obs/ft)
0.02% obs/m
(0.0062% obs/ft)
Min.
Access
Level
ADM
Maximum
10 seconds
15 seconds
23