Xtralis VESDA LCD Programmer Product Guide
Scrn
Description
No.
74.
Relay Assignments - Each relay is allocated a screen. In their respective screens
assign the relevant alarm, fault, scanning or isolate function. Multiple functions can
be assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent
Fault and Fire 1 functions respectively. Additional functions may be assigned to
Relays 3 and 6. Use the
75.
Diagnostics - It is possible to conduct alarm and fault tests through sub-menus of
this screen.
Alarm Test - This causes the detector to generate a Fire 2 condition
Fault Test - This causes a system fault for 30 seconds
Flow Fault - This causes a 30 second Air Flow fault
Sector Test - This allows all valves to be forced closed and open
Scan Test - This will perform a scan test
Relay Test - (Refer to Screen 76).
76.
Relay Test - This allows testing each relay by turning it ON and OFF.
77.
Factory Defaults -
Factory Defaults - To restore factory defaults, highlight Restore and press
Defaults OK - Highlighting Start and pressing
Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
28
key to assign or de-assign functions.
Parameter
Scanning
Sector 4
Sector 3
Sector 2
Sector 1
Fire 2
Fire 1
Action
Alert
Urgent Fault
Minor Fault
Isolate
Default
Relay 12
Relay 11
Relay 10
Relay 9
Relay 8
Relay 7
Relay 6
Relay 5
Relay 4
Relay 3
Relay 2
Relay 1
will acknowledge Factory
Xtralis VESDA
®
Min.
Access
Level
ADM
ADM
ADM
DST
.
ADM
www.xtralis.com