Xtralis VESDA LCD Programmer Module Product Manual page 41

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
109.
Address Control - The four functions under Address Control are the same as the
functions performed by the buttons on the Display Module.
Mode - This controls the mode of the LCD Numerical display on the Display.
Use the +, -, and the
-
Current Sector - Display the First Alarm Sector in VLS Display
-
Sensitivity - Displays the sensitivity level
-
Smoke Level - Displays the current smoke level
-
Address Number - Displays the assigned VESDA Zone number for the
detector
Silence - Silences beeping sound of the detector
Scan - Selecting this option in a VLS Display commences a Scan sequence of
the assigned VLS Detector
Reset - Resets faults
Isolate - Starts and stops isolation of the detector
110.
Address Number - Assign the VESDA Zone number to a Display/Relay.
111.
Location - Allocate a VESDA Zone name and location and assign these to the
respective Display/Relay.
112.
Power Supply Number - Input the number of the power supply that is assigned to
the detector. If the VESDA Intelligent Power Supply is not being used enter "0".
113.
Button Lockout - This screen provides the option to Lock or enable the buttons on
a Display.
114.
Relays/Disp Connected - Use the screen to enter the number of relays connected
to the Display. It also indicates if the detector is a VLS.
115.
Relay Setup - This displays sub-menus for:
Relay Startup Mode (only used on a display with relays assigned)
Latching
Beeper
Relay Assignments (only used on a display with relays assigned)
116.
Relay Startup Mode - Displays the energize/de-energized condition for each relay.
If required, use the
relays.
www.xtralis.com
key to change the mode
+ -
and
keys to change the energized/de-energized state of
Parameter
Relay Startup Mode
Relay 2 & 3 energized
Relays 1, 4-7 (4-12)
Xtralis VESDA LCD Programmer Product Guide
Default
Energized
De-Energized
Min.
Access
Level
USR
ADM
ADM
ADM
ADM
DST
ADM
ADM
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lcd programmer hand heldLcd programmer remote

Table of Contents