Xtralis VESDA LCD Programmer Module Product Manual page 43

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
119.
Relay Assignments - Each relay is allocated a screen. In their respective screens
assign the relevant alarm, fault, scanning or isolate function. Multiple functions can
be assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent
Fault and Fire 1 functions respectively. Additional functions may be assigned to
Relays 3 and 6. Use the
120.
Factory Defaults -
Factory Defaults - To restore factory defaults, highlight Restore and press
Defaults OK - Highlighting Start and pressing
Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
121.
Communications - The Communications screen allows settings for:
Net Delay - This function sets the maximum time for a message to travel around
the network and return to the originating device. If the message does not return
within the prescribed time, it is presumed lost and will be resent
Pref. Port - This allows you to assign a preferred port for communication
Health Check - This function sets the frequency of health-check messages sent
around the system
Open-ended - In an open ended VESDAnet loop select the port that is not
connected to the VESDAnet loop.
Parameter
Network delay
Preferred port
Health check
Open - ended
www.xtralis.com
Xtralis VESDA LCD Programmer Product Guide
key to assign or de-assign functions.
Parameter
Scanning
Sector 4
Sector 3
Sector 2
Sector 1
Fire 2
Fire 1
Action
Alert
Urgent Fault
Minor Fault
Isolate
Default
Minimum
15 seconds
10 seconds
A
N/A
45 seconds
40 seconds
none
N/A
Default
Relay 12
Relay 11
Relay 10
Relay 9
Relay 8
Relay 7
Relay 6
Relay 5
Relay 4
Relay 3
Relay 2
Relay 1
will acknowledge Factory
Maximum
45 seconds
N/A
60 seconds
N/A
Min.
Access
Level
ADM
DST
.
ADM
DST
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lcd programmer hand heldLcd programmer remote

Table of Contents