Xtralis VESDA LCD Programmer Module Product Manual page 39

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
96.
Filter - Displays details on the life and usage of the filter. When the filter is replaced
with a new filter, highlight Start and press
for replacement. The service interval for filter replacements can be entered to suit
the ambient conditions of the VESDA Zone in which the detector is installed.
Life Used
Date Due
Service Interval
New Filter
Dust Count
Dust Limit
Default: 1825 days (5 years), Min. 1 day, Max 3655 days (10 years)
97.
Reference Detector - If a reference detector is connected to VESDAnet, enter the:
Reference Address Number
Dilution Factor - This is the amount of offset required from the reference
detector. Setting it to 100% will cause the detector to ignore the same amount
of smoke as is being detected by the reference detector. Setting it to 50%
ignores half of the smoke detected at the reference detector. These settings
allow you to fine tune how much of the smoke detected by the reference
detector is also likely to reach each detector.
Delay - The amount of time it will take smoke to move from the reference
detector to the other detectors.
Parameter
Reference Address No
Dilution
Delay
98.
Rebuild Address List - Highlight start and press
Use this option to rebuild the Address List after removing a display module
assigned to the detector.
99.
Power Supply Number - Input the number of the power supply that is assigned to
the detector. If the Intelligent Power Supply is not being used enter "0".
100.
Button Lockout - This screen provides the option to Lock or enable the Reset/
Isolate Button on the VLC.
101.
Diagnostics - It is possible to conduct alarm and fault tests through sub-menus of
this screen.
Alarm Test - This causes the detector to generate a Fire condition
Fault Test - This causes a system fault for 30 seconds
Flow Fault - Turns the aspirator off for 30 seconds causing an air flow fault.
(This causes the LED's to light up)
Lamp Test - This causes the LCDs to light up
Relay Test - (refer to Screen 102).
102.
Relay Test - This allows testing each relay by turning it ON and OFF.
www.xtralis.com
Xtralis VESDA LCD Programmer Product Guide
to restart the dust count and due date
Default
Minimum
255
Selectable
100%
1%
2 minutes
0 minutes
to rebuild the Address List.
Min.
Access
Level
ADM
DST
DST
ADM
Maximum
Selectable
100%
15 minutes
ADM
ADM
ADM
ADM
ADM
33