Xtralis VESDA
LCD Programmer
Product Guide
Document Number: 10194_05
Part Number: 30004

Advertisement

Table of Contents
loading

Summary of Contents for Xtralis VESDA LCD Programmer Module

  • Page 1 Xtralis VESDA LCD Programmer Product Guide Document Number: 10194_05 Part Number: 30004...
  • Page 3 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Intellectual Property and Copyright This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners. Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
  • Page 4 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Document Conventions The following typographic conventions are used in this document. Convention Description Bold Used to denote: emphasis Used for names of menus, menu options, toolbar buttons Italics Used to denote: references to other parts of this document or other documents.
  • Page 5 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Codes and Standards Information for Air Sampling Smoke Detection We strongly recommend that this document is read in conjunction with the appropriate local codes and standards for smoke detection and electrical connections. This document contains generic product information and some sections may not comply with all local codes and standards.
  • Page 6 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® www.xtralis.com...
  • Page 7: Table Of Contents

    Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Contents 1. Scope ............................3 2. Introduction to LCD Programmer ....................3 Features of LCD Programmer ....................3 3. Product Information ........................3 Product Specifications ......................5 The LCD Programmer Keys ....................6 4. User Access Levels and PIN ......................6 User Access Level ........................6...
  • Page 8 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® www.xtralis.com...
  • Page 9: Scope

    Xtralis VESDA system. 2 Introduction to LCD Programmer The LCD Programmer interfaces with most of the Xtralis VESDA family of products through VESDAnet. The Xtralis VESDA VLC-500 (RO), System Relay Module and AOM cannot be programmed using the LCD Programmer.
  • Page 10 Xtralis VESDA LCD Programmer Product Guide ® The LCD Programmer module can be placed either in the center or the right plate of a VLP or VLS detector Front Cover, or in an Xtralis VESDA Remote Mounting System. For further information see the Xtralis VESDA Remote Systems Product Guide.
  • Page 11: Product Specifications

    Default User Level ADM = Administrator DST = Distributor 3 character User Level ID Security Access 4 digit individual Personal Identification Number (PIN) (Default PIN is available with Xtralis VESDA Distributors) Operating Ambient: 0 to 39 C (32 to 103...
  • Page 12: The Lcd Programmer Keys

    Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Terminal Connector 15 pin D-type RS485 VESDAnet to Head Processor connector. field wiring to Card or to VESDAnet cable screw terminals Connections: expansion required. Connects blocks (0.2 - 2.5 connector on...
  • Page 13: Personal Identification Number (Pin)

    PIN number three times they will not be allowed another attempt for ten minutes. A four digit number and an Xtralis VESDA contact phone number will be displayed on the screen. No further entries can be made until instructions are received from Xtralis.
  • Page 14: Navigating The Lcd Programmer

    Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Navigating the LCD Programmer To navigate the menu tree of the LCD Programmer, to change or view parameters, and to execute system functions, use the eight keys described in the table below.
  • Page 15: Intentional Log Off

    Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Intentional Log Off To log off the system: 1. Press the key until the Log Off warning screen is displayed 2. Confirm the Log Off with a 3. The LCD Programmer will display the LOGON screen 4.
  • Page 16 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® 41. VLS Detector 42. Status 43. Scan Status 44. Event Log 45. View Events 46. Select Events 47. Zone Control 48. Smoke Thresholds 49. Day Thresholds 50. Night Thresholds 51. Change-Over Times 52.
  • Page 17 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide From Screen 80. VLC Detector From Screen 3 5 & 139 81. Status 82. Event Log 83. View Events 84. Select Events 85. Zone Control 86. Smoke Thresholds 87. Smoke Thresholds 88.
  • Page 18 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® 123. Programmer 124. Status 125. Zone Number 126. Location 127. Power Supply Number 128. Zone Control Lockout 129. Factory Defaults 130. Communications 131. Miscellaneous 132. HLI 133. Status 140. System/ 134. Location All Device 135.
  • Page 19: Lcd Programmer Screen Description

    PIN field. Use the keys to enter the PIN VLP - This screen displays options available for accessing and managing the parameters of Xtralis VESDA range of products connected to VESDAnet. The Options are: • Setup By Address •...
  • Page 20 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Select Events - This function assists in easier viewing of the logged events. The events can be sorted as per the categories displayed. After selecting the events, proceed to Screen 9 to view the events.
  • Page 21 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Night Thresholds - This screen allows viewing and changing the current Fire 2, Fire 1, Action and Alert thresholds for night time. Parameter Default Minimum Maximum Fire 2/Full Scale 2.000% obs/m...
  • Page 22 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Smoke Change - The change in obscuration rate mentioned here will register the event in the event log. This is subject to the change occurring over the interval period that is input.
  • Page 23 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Flow Control - Allows you to change the aspirator speed for VLP and VLS. Enter the pipes in use by placing a against the respective pipe. Default: 3000rpm, Min.
  • Page 24 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Relay Startup Mode - Displays the energize/de-energized condition for each relay. ↵ If required, use the keys to change the energized/de-energized state of relays. Parameter Default Relay Startup Mode Relay 2 &...
  • Page 25 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Relay Assignments - Each relay is allocated a screen. In their respective screens assign the relevant alarm, fault or isolate function. Multiple functions can be assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent Fault and Fire 1 functions respectively.
  • Page 26 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Miscellaneous - • UL Version - A against this indicates that the device is set to meet UL specifications. • Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms •...
  • Page 27 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Select Events - This function assists in easier viewing of the logged events. The events can be sorted as per the categories displayed. After selecting the events, proceed to Screen 45 to view the events.
  • Page 28 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Night Thresholds - This screen allows viewing and changing the current Fire 2, Fire 1, Action and Alert thresholds for night time. Parameter Default Minimum Maximum Fire 2 2.000% obs/m...
  • Page 29 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Delays & Thresholds - This screen displays the delays and thresholds for the VLS. Delays - The time before a VLS will commence scanning, once the lowest threshold is reached.
  • Page 30 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Sector Factor (Sectors 1 to 4) - • Sector Factor - Set the sector factor between 0.5 and 2 Parameter Default Minimum Maximum Factor 1.000 0.500 2.000...
  • Page 31 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level AutoLearn - The AutoLearn function allows setting the thresholds automatically. The detector measures the ambient smoke levels over the set period and will establish the smoke and alarm thresholds accordingly. Enter the number of days, hours and minutes over which the AutoLearn function is to apply.
  • Page 32 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Filter - Displays details on the life and usage of the filter. When the filter is replaced ↵ with a new filter, highlight Start and press to restart the dust count and due date for replacement.
  • Page 33 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Relay Startup Mode - Displays the energize/de-energized condition for each relay. ↵ If required, use the and press keys to change the energized/de-energized state of relays.
  • Page 34 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Relay Assignments - Each relay is allocated a screen. In their respective screens assign the relevant alarm, fault, scanning or isolate function. Multiple functions can be assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent Fault and Fire 1 functions respectively.
  • Page 35 • Alarms - If the detector is in an alarm mode, the alarm stage is displayed • Faults - List of faults generated for each Xtralis VESDA device assigned to the Address • Isolated - The Isolated status is reported only if the detector has been isolated •...
  • Page 36 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level Select Events - This function assists in easier viewing of the logged events. The events can be sorted as per the categories displayed. After selecting the events, proceed to Screen 83 to view the events.
  • Page 37 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Smoke Thresholds - This screen lists the available options for setting smoke thresholds. • Fire • Pre-Alarm • Alert • Overlay Alert Parameter Default Minimum Maximum Fire 1/Fire 0.200% obs/m...
  • Page 38 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level AutoLearn - The AutoLearn function allows setting the thresholds automatically. The detector measures the ambient over the set period and will establish the smoke thresholds accordingly. Enter the number of days, hours and minutes over which the AutoLearn function is to run.
  • Page 39 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level Filter - Displays details on the life and usage of the filter. When the filter is replaced ↵ with a new filter, highlight Start and press to restart the dust count and due date for replacement.
  • Page 40 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level 103. Factory Defaults - ↵ • Factory Defaults - To restore factory defaults, highlight Restore and press ↵ • Defaults OK - Highlighting Start and pressing will acknowledge Factory Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
  • Page 41 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level 109. Address Control - The four functions under Address Control are the same as the functions performed by the buttons on the Display Module. • Mode - This controls the mode of the LCD Numerical display on the Display.
  • Page 42 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level 117. Latching - This screen displays the latched/unlatched relay condition for different levels of alarms in each sector, faults and scanning. In the latched condition the reporting of an alarm or a fault continues to be reported even after the event is over.
  • Page 43 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level 119. Relay Assignments - Each relay is allocated a screen. In their respective screens assign the relevant alarm, fault, scanning or isolate function. Multiple functions can be assigned to each relay.
  • Page 44 Xtralis VESDA Xtralis VESDA LCD Programmer Product Guide ® Min. Scrn Description Access Level 122. Miscellaneous - • Isolate remind - Provides an option to enable or disable the Beeper reminder for Isolate function • Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms •...
  • Page 45 138. Setup By Type - The Setup By Type selection allows accessing and managing the properties of all Xtralis VESDA devices connected to VESDAnet. This screen lists all the Xtralis VESDA products connected to the VESDAnet. Highlight the required ↵...
  • Page 46 Access Level 139. VESDA Device - This screen lists all devices of a particular Xtralis VESDA product (e.g. Each VLP detector connected to VESDAnet will be displayed with their respective unique detector number under the VLP/VLS screen). To access ↵...
  • Page 47 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Min. Scrn Description Access Level 148. Change User Details - This screen displays the current user ID and PIN. The User USR/ ID and PIN can be changed in this screen. The Access level cannot be changed.
  • Page 48 • Latch Faults - This provides a YES/NO option to latch/unlatch all Faults 158. Show Wiring Order - Lists all the Xtralis VESDA devices connected to VESDAnet. 159. LCD Screen - Select this menu to set LCD screen options. 160.
  • Page 49 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide Index ..........36 Beeper ......33, 35 Button Lockout ......41 System/All Devices ..........15 Action Add User ....41 Users - System/All Devices ......14, 21 Address Control ........20, 29 Cfg Code ......
  • Page 50 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide ......23 Delays & Thresholds Delete User ....41 Users - System/All Devices ......... 20, 29, 34 GP Input Devices ......... 5 Maximum ......19, 28, 33 Diagnostics ..........6 ........... 5...
  • Page 51 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide ..39 ....... 39 Miscellaneous - LCD Programmer Communications - HLI ..39 Communications - LCD Programmer ......... 18, 27, 36 Latching ......5 Operating Temperature ......... 38 LCD Programmer ........31 Overlay Alert ......
  • Page 52 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide ........... 28 Scan Test Sub-Node Type ..........22 ........39 Scanner Status - HLI ........5 Screen Control Supply Voltage ........42 LCD Screen Support ........5 ..39 Screen Display Miscellaneous - LCD Programmer ........
  • Page 53 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide ........20, 29 ......13 View Events Status Cfg Code ....... 13 Status Current % flow ........13 Status Faults ...... 32 ........ 13 Address name/location Status Isolated ......32 ......13...
  • Page 54 Xtralis VESDA ® Xtralis VESDA LCD Programmer Product Guide ......27 ..........5 Relay Startup Mode Voltage ........28 Relay test ..... 26 Relays/disp Connected ..........21 Reset ........20 Scan Status ........28 Scan test ........15, 22 Weekend .........