Xtralis VESDA LCD Programmer Module Product Manual page 37

Table of Contents

Advertisement

Xtralis VESDA
®
Scrn
Description
No.
87.
Smoke Thresholds - This screen lists the available options for setting smoke
thresholds.
Fire
Pre-Alarm
Alert
Overlay Alert
Parameter
Fire 1/Fire
Action/Pre/
Alarm
Alert
88.
Alarm Delays - In this screen insert the required time delay (in seconds) before an
alarm is generated at Fire, Pre-Alarm, Alert, Overlay Alert levels. This screen also
offers the option of simultaneous or cumulative delay times before the alarm is
generated. The instant fire alarm option can be enabled or disabled in this screen.
Parameter
Fire 1/Fire
Action/Pre/Alarm
Alert
Delay Times
Instantaneous Fire
89.
Smoke Change - The change in obscuration rate mentioned here will register the
event in the event log. This is subject to the change occurring over the interval
period that is input. You can input the required obscuration and interval.
Change By
Min. Interval
Parameter
Change By
Min. Interval
www.xtralis.com
Default
Minimum
0.200% obs/m
0.015% obs/m
(0.0625% obs/ft)
(0.0046% obs/ft)
0.140% obs/m
0.010% obs/m
(0.044% obs/ft)
(0.0031 obs/ft)
0.080% obs/m
0.005% obs/m
(0.025% obs/ft)
(0.0015% obs/ft)
Default
10 seconds
10 seconds
10 seconds
Simultaneous
Disabled
Default
Minimum
0.02% obs/m
0.005% obs/m
(0.0062% obs/ft)
(0.0015% obs/ft)
2 seconds
2 seconds
Xtralis VESDA LCD Programmer Product Guide
Maximum
2.000% obs/m
(0.6250% obs/ft)
1.995% obs/m
(0.6234% obs/ft
1.990% obs/m
(0.6218% obs/ft)
Minimum
Maximum
0 seconds
60 seconds
0 seconds
60 seconds
0 seconds
60 seconds
Simultaneous
Cumulative
Enabled
Disabled
Maximum
0.2% obs/m
(0.0625% obs/ft)
10 seconds
Min.
Access
Level
ADM
ADM
ADM
DST
31