Xtralis VESDA LCD Programmer Module Product Manual page 32

Table of Contents

Advertisement

Xtralis VESDA LCD Programmer Product Guide
Scrn
Description
No.
66.
Filter - Displays details on the life and usage of the filter. When the filter is replaced
with a new filter, highlight Start and press
for replacement. The service interval for filter replacements can be entered to suit
the ambient conditions of the VESDA Zone in which the detector is installed.
Life Used
Date Due
Service Interval
New Filter
Dust Count
Dust Limit
Default: 1825 days (5 years), Min. 1 day, Max 3655 days (10 years)
67.
Reference Detector - If a reference detector is connected to VESDAnet, enter the:
Reference Address Number
Dilution Factor - This is the amount of offset required from the reference
detector. Setting it to 100% will cause the detector to ignore the same amount
of smoke as is being detected by the reference detector. Setting it to 50%
ignores half of the smoke detected at the reference detector. These settings
allow you to fine tune how much of the smoke detected by the reference
detector is also likely to reach each detector.
Delay - The amount of time it will take smoke to move from the reference
detector to the other detectors.
Parameter
Reference Address No
Dilution
Delay
68.
Rebuild Address List - Highlight Start and press
Use this option to rebuild the Address List after removing a display module
assigned to the VESDA Detector.
69.
Power Supply Number - Input the number of the power supply that is assigned to
the detector. If the VESDA Intelligent Power Supply is not being used enter "0".
70.
Relays/Disp Connected - This screen displays the number of relays connected to
the detector. It also indicates if the detector is a VLS.
71.
Relay Setup - This screen and its sub-menus allow setting up the assignment of
functions to the relays and to energize or de-energize relays.
26
Default
255
100%
2 minutes
Parameter
Default
Relay card
None
(Display only - 7/12 relay fitted)
to restart the dust count and due date
Minimum
Maximum
Selectable
Selectable
1%
100%
0 minutes
15 minutes
to rebuild the Address List.
Xtralis VESDA
®
Min.
Access
Level
ADM
DST
DST
ADM
ADM
ADM
ADM
ADM
www.xtralis.com