Xtralis VESDA LCD Programmer Module Product Manual page 28

Table of Contents

Advertisement

Xtralis VESDA LCD Programmer Product Guide
Scrn
Description
No.
50.
Night Thresholds - This screen allows viewing and changing the current Fire 2,
Fire 1, Action and Alert thresholds for night time.
Parameter
Fire 2
Fire 1
Action/Pre/
Alarm
Alert
51.
Change-Over Times - Insert the time to switch from day to night thresholds and
night to day thresholds. Day Start and Night Start have been defaulted at 07:00:00
and 19:00:00 respectively.
52.
Weekend - Placing a
weekend. By default Saturday and Sunday are set as weekend days.
53.
Holidays - Insert the first and the last day of holidays to set the night fire
thresholds during this period.
54.
Scanner - The Scanner Menu has 3 sub-menus for:
Scanner Delays & Thresholds
Sector Factor (Sectors 1 to 4)
Valve Operations
22
Default
Minimum
2.000% obs/m
0.020% obs/m
(0.625% obs/ft)
(0.0062% obs/ft)
0.200% obs/m
0.015% obs/m
(0.0625% obs/ft)
(0.0046% obs/ft)
0.140% obs/m
0.010% obs/m
(0.044% obs/ft)
(0.0031 obs/ft)
0.080% obs/m
0.005% obs/m
(0.025% obs/ft)
(0.0015% obs/ft)
against the relevant week day will denote it as being
Xtralis VESDA
Maximum
20.000% obs/m
(6.25% obs/ft)
2.000% obs/m
(0.6250% obs/ft)
1.995% obs/m
(0.6234% obs/ft
1.990% obs/m
(0.6218% obs/ft)
www.xtralis.com
®
Min.
Access
Level
ADM
ADM
ADM
ADM
USR