Note:
All ArcLamp Drivers are factory set to provide 100% output level to all
circuits. This allows an electrical contractor to check that all products are properly
installed and wired. During system commissioning, the certified ETC technician will
remove this setting and configure DMX addresses for normal use. During normal use
after commissioning is complete, ArcLamps will light if the DMX Control level is greater
than 0.

Updating the Driver Firmware

When commissioning a system installation, check all ArcSystem drivers and multi-cell luminaires
to ensure that the latest firmware is present. If the firmware is not up to date, upgrade it
following the instructions below for your luminaire type.

Wireless ArcMesh Luminaires

Upgrade luminaire firmware using the ArcSystem Configuration Software. The fixture firmware
file and ArcSystem Configuration Software are available for free at etcconnect.com.

RDM Luminaires

Upgrade luminaire firmware using ETC Concert and ETC UpdaterAtor software before
commissioning is completed. For more information on UpdaterAtor, download the UpdaterAtor
Software Quick Guide for free at etcconnect.com.
When commissioning a system installation, check all ArcSystem drivers and multi-cell luminaires
to ensure that the latest firmware is present. If the firmware is not up to date, upgrade it using
ETC Concert and ETC UpdaterAtor software before commissioning is completed. For more
information on UpdaterAtor, download the UpdaterAtor Software Quick Guide for free at
etcconnect.com.

ArcLamp with ArcMesh Configuration and Commissioning

Initial system programming of a wireless ArcLamp system requires a USB commissioning tool (ARC-CT)
and existing hardware such as a laptop or desktop computer that is connected to the ArcMesh
network. This programming will be carried out by an ETC certified technician at the time of
system commissioning and training.
The following checklist will be included during the configuration process:
patching groups of fixtures to specific DMX channels
assigning minimum and maximum dimming levels per group
assigning power fail/recovery options per group

ArcLamp RDM Configuration

RDM Values
Manufacturer ID: 0x6574 (Electronic Theatre Controls)
Model IDs
ArcLamp Drivers
ArcLamp Driver 150 0x120E
ArcLamp Driver 350 0x120F