Emergency System One-Cell Installation; Emergency Driver Power Input Wiring - ETC ArcSystem Pro D4 Series Installation Manual

Drivers
Hide thumbs Also See for ArcSystem Pro D4 Series:
Table of Contents

Advertisement

Emergency System One-Cell Installation

With the exception of power input terminations, ArcSystem emergency system installation
requirements are the same as those of the standard ArcSystem. Complete the appropriate steps
for your installation, referencing the following sections for any additional installation details
before wiring the power:
Preparing the Ceiling for Recessed Luminaires on page 12
Installing One-Cell Recessed Luminaires on page 14
Installing One-Cell Yoke-Mounted Luminaires on page 14
D4 Series Wall-Mount Driver Installation on page 15
Installation on page 27

Emergency Driver Power Input Wiring

D4 Emergency Drivers are available for systems requiring emergency lighting control.
Note:
D4 Emergency Drivers require two branch circuit power input connections, normal sense and
maintained (emergency).
Maintained (emergency) provides constant power to the D4 Driver regardless of the state,
enforcing the ability to maintain a lights on condition when needed. The power source
must be connected to an emergency branch circuit with an upstream UL1008 automatic
transfer switch.
Normal sense detects when normal power is present. In the event of a normal power
failure, the D4 Driver will force all output channels on the D4 Driver to full (100%). Any
control of the connected output channels will be unavailable until normal power has been
restored.
Emergency System One-Cell Installation
The installation must conform to local and national codes.
or
D4 Series Rack-Mount Driver
31