If a manual test/equalize, manually initiated timed test/equalize, or automatic equalize is in
process; it is canceled and the system returns to float mode when system ground is removed from the
test/equalize terminal.
Restarting Procedures when Rectifier Module (PCU) is Automatically or Manually
Inhibited, Shut down, or Locked Out

Rectifier Module High Voltage Shutdown and Lockout

Turn AC power to the Rectifier Module off or remove the Rectifier Module, wait 5 seconds or more, then turn
AC power to the Rectifier Module on or re-insert the Rectifier Module. Refer to the "Troubleshooting" section
for a Rectifier Module removal procedure.

Rectifier Module Emergency Shutdown and Fire Alarm Disconnect

Remove the emergency shutdown and fire alarm disconnect signal. Turn AC power to the Rectifier Modules off
then on, or remove and re-insert the Rectifier Modules. Refer to the "Troubleshooting" section for a Rectifier
Module removal procedure.

Remote On/Off (TR)

Remove the remote on/off (TR) signal from the respective Rectifier Module. The signal can originate via the
local MCA Interface Pad.

Restarting a DC-DC Converter Following A High Voltage Shutdown

To restart a DC-DC Converter Module following a high voltage shutdown, remove the Convert Module from the
shelf, wait 5 seconds or more, then re-insert the Converter Module. If the Converter Module immediately shuts
down a second time or fails to start, a fault condition is indicated, and replacement may be necessary. Refer to
the "Troubleshooting" section for replacement information. Refer to the "Troubleshooting" section for a DC-DC
Converter Module removal procedure.
Low Voltage Disconnect Reconnect Procedure (WHEN FURNISHED AND SET FOR
MANUAL RECONNECT)
If the low voltage disconnect circuit(s) is set for manual reconnect, the battery and system output have to be
manually reconnected to the controlled load(s) when the low voltage disconnect circuit activates. (Battery
voltage must be above the upper setting of the low voltage disconnect circuit.) Perform the following
procedure to reconnect the low voltage disconnect circuits.
Procedure
1.
Refer to Figure 1 for control and indicator location.
2.
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton.
3.
Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ALARM LVD ACTIVE".
4.
Press and release the FUNCTION SET ENTER pushbutton.
Vertiv
| +24 VDC Power System User Manual (Section 6013) | Rev. G
58