7.4.2

Paint and insulation

Damage to the paint and insulation during transport and installation must be care-
fully repaired.
Painting
Coating system S 2.15 acc. to EN ISO 12944-5 for environmental conditions C2
acc. to EN ISO 12944-2.
Designed for room temperatures of 5 °C up to 40 °C.
Standard colour of product: RAL 5014 pigeon blue (other colours can be selected
as required.)
Colour of control cabinet / switching cabinet: RAL 7035 light grey
Insulation
The insulation is basically designed for an ambient temperature of 20 °C and a
humidity of 70 %.
7.5

First start - Start-up procedure

The following procedures should be completed in the sequence in which they are
described:
7.5.1

Checking the electrical connection

Check that all electrical work has been carried out in accordance with the stand-
ards (e.g. protective earth, insulation, shielding, covers).
7.5.2

Leak test

See nameplate for permissible operating pressure.
The necessary safety precautions must be taken before performing the leak test.
Prior to the pressure test, the valve positions must be checked.
For testing, perform a pressure loss test for approx. 3 hours with dry nitrogen.
For compressor packages, perform the pressure loss test with a test pressure of
7 bar, for chillers and heat pumps separate by low pressure side or high pressure
side 1 bar below maximum operating pressure.
A pressure drop of 2% is permissible during the 3 hours, while fluctuations of the
ambient temperature must be taken into account.
L_151511_2
19.12.2019
Danger
Contact with live components is prohibited.
► Produce the earth connection according to the designation in the general
assembly drawing. See chapter "Designation of the earth connection".
Warning!
Danger of ammonia!
► For systems with FAT, you must refer to chapter "Measures during shut-
downs"!
Start-up
First start - Start-up procedure
75