Plans

Equipment log

13
Plans
13.1
Equipment log
The equipment log needs to include the following information:
The following documents that are part of the product documentation or this
operating manual can be used for keeping a system log:
112
Notice
Owners or operators of refrigeration equipment or a heat pump with filling
levels of more than 3 kg of refrigerant are required to keep an equipment
log under EN378 Part 2.
► The technical customer service at GEA Refrigeration Germany GmbH of-
fers support in maintaining the equipment log.
► The equipment log needs to be stored for at least five years after manu-
facture and presented to the relevant authorities upon request.
Service and maintenance work,
Proof of a regular leak test,
Quantity and type of the filled or recovered refrigerant including quantitative
balance,
If recovered refrigerant is used, then the
analytical findings
and
the source of the recovered refrigerant
need to be specified.
Quantity and type of the filled or recovered oil including quantitative balance,
Changes to and replacement of components,
Regular and routine inspections with results and dates,
Longer shut-down periods,
Identification of the company or of the technical staff that carried out the serv-
icing/maintenance.
Maintenance manual
Measurement log of operating parameter (template)
Data sheet of oil filling (template)
Data sheet of refrigerant filling (template)
L_151511_2