Design
If electronic safety switching devices are used for pressure limiting, the setting
may deviate from the standard specifications (see EN 378-2) due to the
increased precision.
The safety devices for pressure limiting according to EN 378-2 are the minimum
requirements. Before commissioning, the requirements specified in the local
operational safety regulations must therefore be compared with those of EN
378-2.
The specified test intervals must be observed to ensure proper functioning of the
safety devices for pressure limiting. They are specified in the respective opera-
tional safety regulations.

3.1.4.12 Components installed by the client

42
Notice
When using safety valves for pressure relief, the operator is responsible for:
► dimensioning of the piping,
► safe discharge of refrigerant when the pressure relief device is triggered.
Warning!
GEA Refrigeration Germany GmbH does not assume any liability for arising
damages or for the violation of the safety regulations resulting from the use
of unsuitable materials or a modification to the product that is not included in
the original safety concept.
► The material properties of components and system parts provided by and
monitored by the customer, in particular in the secondary refrigerant and
heat carrier or coolant circuit as well as in the oil circuit, must be suitable for
the fluids flowing there. Furthermore, in the event of modifications to the
product by the customer, the effects upon the safety devices must be
checked.