Four Weeks Before Restarting - GEA RedGenium Operating Instruction

Table of Contents

Advertisement

Decommissioning
Temporary decommissioning
12.3.5

Four weeks before restarting

110
Check the moisture content and ageing condition of the refrigerating machine
oil. Analyse the oil for this purpose. Compare the results of the analysis with
the values for fresh oil. We recommend an oil change after 1 year at the lat-
est. (See maintenance instructions.)
Check the insulation resistance of the drive motors (see the operating manual
for the electric motor).
Run the oil pump (if present) for about 5 minutes.
Check the system for leak tightness.