User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use
Configuring using the LCD
Label ID
Parameter name
PARAMETERS & STATUS
VARIABLES
StU
General > Setup
y01
Main switch
y02
Activate Multipurger
y07
Restore default parameters
SEr
General > Serial settings
SEr
Serial address (Modbus and
CAN)
bAU
Serial baudrate (Modbus)
COM
Serial settings (Modbus)
CMP
Unit config > Compressor
CM3
PDT
CM4
CST
VA5
PLT
VAL
Unit config > Valve settings
V10
Max_PP
LIM
Unit config > Limits settings
CM1
Setpoint
F10
Setpoint
UNI
Service > Unit
UN1
Unit sensor
LOG
Status var > MCX Design Hotspots
C01
Reset Alarms
V02
SystemOnOff
V03
ValveStatus
V04
CompressorStatus
V05
ALARActive
V06
PressTotemp
V07
ValveCount
V08
ComprTime
V09
COmprStartAfter
V10
ResetMem
V12
StatusKL
V13
WaringCompr
V14
ValveSetpoint
V15
ValveClose
© Danfoss | DCS (ms) | 2021.03
By pressing
the main menu will show up with the options below
Description and selection options
Enable IPS Purger
0:OFF
1: ON
Activate IPS to purge multi points
0:NO
1: YES
0: NO
1: YES, restore default parameters
TThe rate at which information is trans-
ferred in the RS485 communication channel
0: 0
1: 12
2: 24
3: 48
4: 96
5: 144
6: 192
7: 288
8: 384
0: 8N1
1: 8E1
2: 8N2
Pull down time of compressor
Delay between purge cycles (single purge)
Alarm for endless purging
Used amount of purge points - part of initial
setup
Pressure threshhold for compressor
Pressure threshhold for compressor
Select metric or imperial units(US)
0: Metric
1: Imperial
Reset alarm
Feedback from the main switch
Feedback from the purge valve - open/
closed
Feedback from the compressor - on/off
Any alarm active indicator
Suction temperature (calculated from
pressure on suction)
The amount of purge valve activations
Remaining time for compressor pull-down
for the actual purge pointr cycle
The delay between the purging cycles
Recommend default setting only - All
logged values are reset
0: NO
1: YES
Status of KL01 relay (compressor and crank-
case heater)
Indicates problem with compressor status
Temperature threshhold for the opening of
the main purge valve
Temperature threshhold for the closing of
the main purge valve
MIN
MAX
VALUE/TYPE
0
1
0 - OFF
0
1
1 - YES
0
1
0 - NO
1
100
1
0
8
6 - 192
0
2
1 - 8E1
1
0
45
180
2000
1440
4
768
24
0
8
8
5
12
6.5
70
174
94.0
0
1
0 - Metric
0
2
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-327,7
327,7
0.0
-2147483648
2147483647
0
-2147483648
2147483647
0
-2147483648
2147483647
0
0
1
0
-32768
32767
0
-32768
32767
0
-2147483648
2147483647
0
-2147483648
2147483647
0
UNIT
RW
Modbus
address
RW
3001
RW
3002
RW
3003
RW
3007
RW
3008
RW
3009
min
RW
3014
min
RW
3015
h
RW
3016
RW
3024
bar
RW
3052
Psi
RW
3053
RW
3056
RW
1859
Read
8101
Read
8102
RW
8103
Read
8104
Read
8105
Read
8107
Read
8109
Read
8111
RW
9901
Read
8115
Read
8116
Read
8117
Read
8119
BC344024774466en-000201 | 21