User Guide Intelligent Purging System (IPS 8) for Ammonia Technical data, installation and use 148R9645 148R9645 ir.danfoss.com ir.danfoss.com...
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Contents Legal notice ...........................................3 Technical data ..........................................4 Ordering ............................................4 Introduction ..........................................5 Features ............................................5 Working principle ........................................6 Working cycle ..........................................7 Air traps ............................................8 Connection locations ......................................9 Connection points .........................................11...
Title: Product Manager Danfoss only vouches for the correctness of the English version of this declaration. In the event of the declaration being translated into any other language, the translator concerned shall be liable for the correctness of the translation...
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Technical data Supply voltage 230V AC, 1ph, 50Hz Current 5.7 A (max. 6.5 A) Power consumption max. 1.3 kW Short-circuit current rating Icc 10kA Temperature range ambient -10 °C to +43 °C (14 °F to 109 °F)
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Introduction The Danfoss Intelligent Purging System (IPS 8) independent of the main ammonia system and is a stand-alone, self-contained purging unit with only one flange connection to the ammonia designed to remove non-condensable gases plant.
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Working principle The Danfoss IPS 8 is factory-tested and ready to By condensing the ammonia gas, a new use in ammonia plants with a condenser pressure ammonia/NC gases mix is naturally pulled of more than 6,5 bar (94 psi).
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Working cycle The Danfoss IPS 8 operates in 24-hour cycles, of this to be a high concentration of NC gases which 45 minutes are dedicated to an R452A pull and opens the purge solenoid valve.
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Air traps Fig. 4 Liquid level. Bottom connected receiver Fig. 5 Liquid level. Top connected receiver For systems with low pressure liquid level control,...
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Connection locations Air purger installation in a low-pressure liquid level controlled installation The correct locations for the air purger to be the condenser will be short-circuited.
Page 10
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Connection locations Air purger installation in a high-pressure liquid level controlled installation (continued) The ammonia liquid condensed in the air purger For systems with a high-pressure liquid level must be drained through drain pipe (c) to the LP control, the air will collect in the float valve (3).
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Connection points Multi-point purging Single point purging setup is possible (Fig. 09) i.e. NEVER HAVE MORE THAN 1 PURGE POINT OPEN AT A TIME.
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Installation The Danfoss IPS 8 must be installed in Use all 4 lifting eyes and suitable lifting gear accordance with locations recommended in the during installation (unit weight = 100 kg/220 lbs).
Page 13
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Installation (continued) 416,4 Enclosed gasket Enclosed bolts, Torque: 60 Nm (44.3 ft lb) diagonal tension Enclosed weld flange (fig. 14) Purging pipe OD 17.2 for rubber hose to water bath Do not unscrew restrictor inside pipe.
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Electrical wiring The internal wiring of the purger is done at the It is highly recommended that all external cables factory. Only the electrical wiring for the main...
Page 15
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Electrical wiring (continued) 230V AC Press. Switch Compressor Condenser Extraction Crankcase Power supply Power supply air fan heater MCX15B Solenoid valves* *When using GD2 24V DC, remove 1-2 and 3-4 bridges between the terminals and connect power supply Fig.
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Electrical wiring (continued) 24V DC 24V DC R717 High Discharge Suction Temp. pressure pressure Temp. sensor Temp. sensor sensor transmitter transmitter 0V DC 0V DC...
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Quick Startup For the fastest possible system configuration after connecting all purge points to the IPS and following first power up of the IPS, follow these simple instructions: 1.
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Configuring using the LCD By pressing the main menu will show up with the options below Table 02 Main menu navigation Main Menu Submenu...
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus RTU Good Practice The wiring of Modbus RTU (RS485) must be carried out in accordance with the standard ANSI/TIA/EIA-485-A-1998. Galvanic separation shall be provided for segments crossing buildings.
Page 21
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus User Default Unit/ Read/ Modbus Persistent Register Parameter Name Description Min Value Max Value Function Level Value Type Write Data Type Yes/No Code UNIT CONFIG >...
Page 22
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus User Default Unit/ Read/ Modbus Persistent Register Parameter Name Description Min Value Max Value Function Level Value Type Write Data Type Yes/No Code UNIT CONFIG >...
Page 23
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus User Default Unit/ Read/ Modbus Persistent Register Parameter Name Description Min Value Max Value Function Level Value Type Write Data Type Yes/No Code...
Page 24
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus User Default Unit/ Read/ Modbus Persistent Register Parameter Name Description Min Value Max Value Function Level Value Type Write Data Type Yes/No Code...
Page 25
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus User Default Unit/ Read/ Modbus Persistent Register Parameter Name Description Min Value Max Value Function Level Value Type Write Data Type Yes/No Code...
Page 26
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Modbus User Default Unit/ Read/ Modbus Persistent Register Parameter Name Description Min Value Max Value Function Level Value Type Write Data Type Yes/No Code...
User Guide | Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use Maintenance/Service/ Table 05 Disposal Maintenance checklist - Perform once a year minimum Use P&I dagram and check that all powered components are working properly...