User Guide | Intelligent Purging System (IPS 8) Ammonia Ordering Unit Code number 084H5001 Danfoss Intelligent Purging System IPS 8 unit Accessory Spare parts for Accessories/Spare parts (Not included service Code with IPS) (Built-into IPS) 084H5053 Flange blind blank incl Bolts, nuts and Gaskets*...
User Guide | Intelligent Purging System (IPS 8) Ammonia Introduction The Danfoss Intelligent Purging System (IPS 8) independent of the main ammonia system and is a stand-alone, self-contained purging unit with only one flange connection to the ammonia designed to remove non-condensable gases plant.
User Guide | Intelligent Purging System (IPS 8) Ammonia Working principle The Danfoss IPS 8 is factory-tested and ready to By condensing the ammonia gas, a new use in ammonia plants with a condenser pressure ammonia/NC gases mix is naturally pulled of more than 6,5 bar (94 psi).
User Guide | Intelligent Purging System (IPS 8) Ammonia Working cycle The Danfoss IPS 8 operates in 24-hour cycles, of this to be a high concentration of NC gases which 45 minutes are dedicated to an R452A pull and opens the purge solenoid valve. The purge down.
“VClseT” and “VOpenT” The difference between “VClseT” and “VOpenT” is always: 5 ⁰ K (can be changed by Danfoss) If ”Tsat452” < “VOpenT” then Main Purge Valve is ON If “Psat717” is increasing. (here from 6.9 Bar to 7.7) If ”Tsat452”...
User Guide | Intelligent Purging System (IPS 8) Ammonia Connection points Multi-point purging NEVER HAVE MORE THAN 1 PURGE POINT As factory default, the Danfoss IPS 8 is configured to manage up to 8 purge points. (Multi-point OPEN AT A TIME. Always close one purge valve before opening purging.
User Guide | Intelligent Purging System (IPS 8) Ammonia Installation The Danfoss IPS 8 must be installed in Use all 4 lifting eyes and suitable lifting gear accordance with locations recommended in the during installation (unit weight = 100 kg/220 lbs).