Evolution controllers the accessory port is located underneath the controller covered with a decal
labeled Accessory Port 1.
Remove the decal and plug in the harness.
The plug will only fit one way. Do Not force.
The power wires of the harness go directly to the battery.
Reconnect the battery Red (+) and Yellow fused (+) wires, then the two Black (-) wires.
Replace the positive terminal Cover.
Reinstall all covers, check to see that the unit is set to Off mode, reinstall the 7.5A fuse.
Reinstall the T1 fuse and turn on the utility power supply to the transfer switch.
Follow the install wizard instructions to reset the generator date and time.
Place the generator in the AUTO mode, turn off the utility disconnect to simulate an outage.
The generator should crank and start. Let it run approximately 30 seconds, then turn the utility
disconnect back on.
The transfer switch should transfer back to utility and the generator will cool down and turn off.
Verify that the Mobile Link unit's middle LED is illuminated and the bottom LED is illuminated or
flashing at this time.
The top LED will not illuminate until enrollment/activation is complete.