SMM Smart Management Modules
SMM Modules are designed to prevent an overload on the generator when it is supplying the
customer loads.
Up to eight loads can be managed by using SMM Modules.
The SMM Modules manage the loads by shedding the connected loads in the event of a drop in
generator frequency (overload).
Loads to be shed are grouped in 8 priority levels thru a setting on each SMM Module
Generator overload condition is determined by generator frequency.
Loads are shed when the frequency is less than 58Hz for 3 seconds or less than 52Hz for 1/2
second (for 60Hz).
.