How To Wire The Genset - Generac Power Systems PowerPact 6561 Installation Notes

Air-cooled generator
Table of Contents

Advertisement

This section can be found in the Installation Guidelines for Air-cooled Generators, page 21 thru 23.
•Do Not Install the Battery until the Switch and Generator installation is complete.
•The Generator Control board requires 12VDC to operate when the Generator is off.
•If you don't have T1 (120V) from the switch (live) to the Generator Control board.
•The battery will be dead in 2 – 3 days.
•Remove the 7.5A fuse from the control panel and set aside.
Connections to the Generator
RTG-EZ Switch
(The RTG16EZA3 switch is NOT Prewired)
Determine where the 30-foot flexible conduit will pass thru the building to connect to the outdoor
connection box.
Drill a pilot hole to mark the location; then drill the appropriate sized hole with a hole saw.
Then route the 30-foot conduit along the ceiling/floor joists and wall studs to the hole.
The 30-foot flexible conduit may be lengthened a maximum of 15 feet using the same conductor size
and conduit diameter.
If more than 45 feet is required, replace the entire whip with the appropriate conductor and conduit.
The 5-foot conduit cannot be lengthened either and must be replaced if longer length is required.
Connecting from Inside to Outside
From inside the building, feed the end of the 30-foot conduit thru the hole.
Remove the internal cover plate from the outdoor connection box, remove the knockout in the lower
right corner of the box and feed the 30-foot conduit wires into the box.
Attach the conduit to the box; mount the box to the outside wall to conceal the hole.
Use silicone caulk to seal the hole from the inside and outside of the building; also caulk around the
edges of the box to seal it to the building.
Connect to lugs black to black, white to white and red to red, torque to 20 in-lbs. Snap the 4 pin and 2
pin connectors together.
Attach ground wire (Grn) from the conduit to the ground lug, torque to 45 in-lbs.
Wiring the Generator