The Demand regulator on the 8kW single cylinder generator only has one side. The twin cylinder 11 - 20kW
units have a two sided regulator.
Plumbing the Generator
The Generator must be plumbed directly from the source, NOT off the end or tee of an existing
system.
Supply the Generator with 100% loaded BTU-rated fuel supply and pipe size.
A minimum of one approved FULL FLOW manual shutoff valve must be installed in the gaseous fuel
supply line.
The valve must be easily accessible (not hidden under decks etc.). Local codes determine the proper
location.
A - Is a Full Flow Shutoff Valve. B - Is a Full Flow Shutoff Valve with a manometer port for making fuel
pressure checks without going into the generator enclosure.